SmartPLC DataLine with EtherNet/IP device interface
58
>
Change an AS-i slave address
41534
To change the address of an AS-i slave:
1 Select the menu page
►
>
or
>
►
Select an AS-i slave (→
Slave selector
(→ S.
►
Select [Setup] tab.
2 Change the address of the AS-i slave
►
Press the [Change slave address] button.
>
The page displays an overview of the free AS-i addresses (→
Overview of free slave addresses
►
Select the address to be assigned to the AS-i slave and confirm with [Select] function key.
>
Security prompt appears.
►
Press [OK] to confirm the security prompt.
>
The AS-i slave has a new address.
>
The page displays an overview of the AS-i slave states (→
Overview of slave states
3 Optional: change further AS-i addresses.
►
Repeat step 2 to change further AS-i slave addresses.
After the address change, the present configuration (LDS) no longer corresponds to the stored
configuration (LPS).
>
The OSC displays a configuration error.
To remove the configuration error:
► start a projection adaptation (→
Carry out a projection adaptation
(
>
Change an AS-i slave parameter output
41599
To change the parameter output of an AS-i slave:
1 Enable manual access to the outputs
►
Set [Output access] parameter = Manual (→
Set the output access
2 Select the menu page
►
>
or
>
►
Select an AS-i slave (→
Slave selector
(→ S.
►
Select [Setup] tab.
3 Change the parameter output of the AS-i slave
>
The [Parameter output] group displays the current assignment of the parameter output (binary and hexadecimal
representation).
►
Adjust the desired output value one position at a time.
>
Selected value is applied.