SmartPLC DataLine with EtherNet/IP device interface
144
>
Device-specific parameters
41582
Data points in the
configuration assembly
Possible
setting values
[hex]
Default values
when using EDS
file
Description
with EDS
without
EDS
AC1421 AC1422
C.Failsafe state
n=60
00
X
X
Reset AS-i outputs
01
Hold AS-i outputs
C.Swap byteorder
n=61
00
X
X
deactivated
01
activated
C.Analogue
channels IN
n=62
01
1 channel
02
2 channels
04
X
X
4 channels
0B
1 channel per A/B
C.Analogue
channels OUT
n=63
01
1 channel
02
2 channels
04
X
X
4 channels
0B
1 channel per A/B
C.Analogue IN
order
1
n=64
00
X
X
deactivated
01
activated
C.1st analogue IN
Slot 9
2
n=65
41 ... 5F
41
41
AS-i 1 slave
1
... 31
81 ... 9F
AS-i 2 slave 1... 31
C.2nd analogue IN
Slot 9
2
n=66
41 ... 5F
42
42
AS-i 1 slave 1,
2
... 31
81 ... 9F
AS-i 2 slave 1... 31
C.3rd analogue IN
Slot 9
2
n=67
41 ... 5F
43
43
AS-i 1 slave 1 ...
3
... 31
81 ... 9F
AS-i 2 slave 1 ... 31
C.4th analogue IN
Slot 9
2
n=68
41 ... 5F
44
44
AS-i 1 slave 1 ...
4
... 31
81 ... 9F
AS-i 2 slave 1 ... 31
C.5th analogue IN
Slot 9
2
n=69
41 ... 5F
45
45
AS-i 1 slave 1 ...
5
... 31
81 ... 9F
AS-i 2 slave 1 ... 31
C.6th analogue IN
Slot 9
2
n=70
41 ... 5F
46
46
AS-i 1 slave 1 ...
6
... 31
81 ... 9F
AS-i 2 slave 1... 31
C.7th analogue IN
Slot 9
2
n=71
41 ... 5F
47
47
AS-i 1 slave 1 ...
7
.... 31
81 ... 9F
AS-i 2 slave 1 ... 31
C.8th analogue IN
Slot 9
2
n=72
41 ... 5F
48
48
AS-i 1 slave 1 ..
8
... 31
81 ... 9F
AS-i 2 slave 1 ... 31
C.9th analogue IN
Slot 9
2
n=73
41 ... 5F
49
49
AS-i 1 slave 1 ...
9
... 31
81 ... 9F
AS-i 2 slave 1 ... 31
C.10th analogue IN
Slot 9
2
n=74
41 ... 5F
4A
4A
AS-i 1 slave 1 ...
10
... 31
81 ... 9F
AS-i 2 slave 1 ... 31
C.11th analogue IN
Slot 9
2
n=75
41 ... 5F
4B
4B
AS-i 1 slave 1 ...
11
... 31
81 ... 9F
AS-i 2 slave 1 ... 31