67
Part 1 Specification
I/O Signal List
Signal type
Bit
Signal name
Description
Details
Current position
data
32-bit
data
-
The current position data is output as a hexadecimal number
using a 32-bit signed integer (unit: 0.01 mm).
Example) If the data is +25.4 mm, “000009ECH”
(decimal number: 2540) is output.
z
Since a negative value is indicated as a 2’s complement, the
most significant bit becomes “1.”
3.8.3 (5)
Actual motor
current
32-bit
data
-
The actual motor current data is output as a hexadecimal
number using a 32-bit signed integer (unit: mA).
Example) If the data is +1 A (1000 mA), “000003EH8
(decimal number: 1000) is output.
z
Since a negative value is indicated as a 2’s complement, the
most significant bit becomes “1.”
3.8.3 (5)
Current speed
16-bit
data
-
Output as a hexadecimal number using a 16-bit integer
(unit: 1.0 mm/sec).
Example) If the data is 200 mm/sec, “00C8H”
(decimal number: 200) is output.
3.8.3 (5)
Alarm code
16-bit
data
-
The present alarm code is output. (The ALM is turned ON.)
Refer to the list in 3.7.5 for the alarm details. Take note that
these are not simple alarm codes.
3.7.5
b15
EMGS
Emergency stop mode
3.8.2 (2)
b14
CRDY
Controller ready
3.8.2 (1)
b13
ZONE2
Zone output monitor 2
b12
ZONE1
Zone output monitor 1
3.8.2 (13)
b11
-
Cannot be used.
-
b10
-
Cannot be used.
-
b9-b7
-
Cannot be used.
-
b6
-
Cannot be used.
-
b5
PSFL
Missed load in push operation
3.8.3 (5)
3.8.4 (1)
b4
SV
Ready (servo ON)
3.8.2 (5)
b3 ALM
Alarm
present
3.8.2
(3)
b2 MOVE
Moving
3.8.2
(8)
b1
HEND
Home return complete
3.8.2 (6)
PLC input
Status signal
b0
PEND
Position complete
3.8.2 (9)
Содержание RoboNet
Страница 1: ...Operation Manual Forth Edition ROBONET ...
Страница 242: ...222 Part 1 Specification 5 4 3 External Dimensions 50 from DIN rail center 35 mm DIN rail 69 3 from DIN rail surface ...
Страница 257: ...237 Part 2 Startup Chapter X Installed face down X Installed face up ...
Страница 354: ...334 ...
Страница 395: ...375 ...
Страница 396: ...376 ...
Страница 397: ...377 ...