345
Part 3 Maintenance
1.2.2 Alarms by Field Network Type
The alarms indicated by the STATUS0 and STATUS1 LEDs vary depending on the field network type, as shown below.
(1) CC-Link
LED name
Displayed
color
Condition Action
Unlit [1]
Normal
[2] Reset process is in progress.
-
-
Orange
[1] CRC error (*1)
[2] A station number setting error
occurred after a reset. (*2)
[3] A baud rate setting error occurred
after a reset. (*3)
[1] Noise in the communication line or
disconnected communication cable is
suspected, among others. Check the
applicable items and take an
appropriate action.
[2] Review the station number setting.
[3] Set the MODE switch on the master
side to 4 or smaller.
STATUS-1
Blinking
orange
(0.4 sec)
The station number or baud rate changed
from the specified value after a reset.
-
Green
[1] Refresh or polling data was received
successfully after joining the network.
[2] Refresh data was received
successfully.
-
STATUS-0
Unlit
[1] The unit is yet to join the network.
[2] Channel carrier waves were detected.
[3] A
timeout
occurred.
[4] Reset process is in progress.
This condition indicates that the unit is
offline, meaning that it is not linked to the
host master.
Check the power supplies of the master
and gateway unit, communication cable,
station number and baud rate settings of
the gateway unit, and network parameter
settings of the master.
(*1) CRC: Cyclic Redundancy Check
A data error detection method widely used in synchronous transmission.
(*2) Since the station number of the master is normally set to 0, the setting range is 1 to 64. The number of stations,
including occupied stations, must not exceed 64.
(*3) The GateWayR unit and master communicate with each other when the master is in the online mode. In the
online mode, the MODE switch on the master is set to any one of 0 to 4 (when QJ61BT11N is used).
Содержание RoboNet
Страница 1: ...Operation Manual Forth Edition ROBONET ...
Страница 242: ...222 Part 1 Specification 5 4 3 External Dimensions 50 from DIN rail center 35 mm DIN rail 69 3 from DIN rail surface ...
Страница 257: ...237 Part 2 Startup Chapter X Installed face down X Installed face up ...
Страница 354: ...334 ...
Страница 395: ...375 ...
Страница 396: ...376 ...
Страница 397: ...377 ...