N700E INSTRUCTION MANUAL
7-2
Symptom/condition
Probable Cause
Countermeasure
Inverter
data is
not
correct
No down-
loadshave
occurred.
•Was power turned off after a parameter
edit but before pressing the store key?
•Edit the data and press the
store key once
•Edits to data are permanently stored at
power down.
Was the time from power off to power
on less than six seconds?
•Wait six seconds or more before
turning power offafter editing data.
A param-
eter will
not
change
after an
edit
(reverts
to old
setting)
The
frequency
setting
will not
change.
Run/Stop
does not
operate.
•Was the standard operatormode and
terminal modechanged correctly?
•Make sure the setting mode of
[A01], [A02] is changed
Truefor all
parameters.
•If you're using the[SET] intelligent input
selection [b09] is the [SFT]
•Is switch 4(located on the back of the
remote operator copy unit) on?
•Change the state of the SFTinput,
and check the b09 parameter.
(b09=0)
•Turn the switch off
Precautions for data setting
When changing any set data and pressing (STR)key to store the data, keep the equipment
un-operated for 6 seconds or more after the selected method is executed.
When any key is pressed, or the reset operation is performed, or the power is turned off within
6 seconds, correct data may not be set.