N700E INSTRUCTION MANUAL
4-28
Func-
code
Name
Run-
time
Edit
Description
Defaults
C17
Output Terminal RN2-RN3
a/b contact setting
X
Select logic convention, two option codes:
0.... a contact(normally open) [NO]
1.... b contact(normally closed) [NC]
0
C18 FM output selection
X
Select function for terminal FM, 3 options
0.... output frequency monitor
1.... output current monitor
2.... output voltage monitor
3.... output power monitor
0
C19 FM gain adjustment
O
Range is 0 to 250.0, resolution is 1
100.0%
C20 FM offset adjustment
O
Range is -3.0 to 10.0%resolution is 0.1
0.0%
C21
Overload advance
notice signallevel setting
X
Sets the overload signal level between 10% and 200%
resolution is 0.1%.
0.1x(Inverter rated current)
∼
2.0x(Inverter rated current)
100.0%
C22
Acceleration arrival signal
frequency setting
X
Sets the frequency arrival setting thres-hold for the
output frequency during acceleration. Setting range is
0.00 to maximum frequency(A04), resolution is0.01Hz
0.00Hz
C23
Deceleration arrival signal
frequency setting
X
Sets the frequency arrival setting threshold for the
output frequency during deceleration, setting range is
0.00 tomaximum frequency(A04) resolution is 0.01Hz
0.00Hz
C24 PID deviation level setting
X
Sets the allowable PID loop error magnitude.
Setting range is 0.0 to 100.0%, resolution is 0.01%
10.0%