N700E INSTRUCTION MANUAL
4-27
Func-
code
Name
Run-
time
Edit
Description
Defaults
Input Terminal Status
C07
Input Terminal 1 a/b contact
setting(NO/NC)
X
Select logic convention, two option codes:
0.... normally open [NO]
1.... normally closed [NC]
0
C08
Input Terminal 2 a/b contact
setting(NO/NC)
X
Select logic convention, two option codes:
0.... normally open [NO]
1.... normally closed [NC].
0
C09
Input Terminal 3 a/b contact
setting(NO/NC)
X
Select logic convention, two option codes:
0.... normally open [NO]
1.... normally closed [NC]
0
C10
Input Terminal 4 a/b contact
setting(NO/NC)
X
Select logic convention, two option codes:
0.... normally open [NO]
1.... Normally closed [NC].
0
C11
Input Terminal 5 a/b contact
setting(NO/NC)
X
Select logic convention, two option codes:
0.... normally open [NO]
1.... Normally closed [NC].
0
C12
Input Terminal 6 a/b contact
setting(NO/NC)
X
Select logic convention, two option codes:
0.... normally open [NO]
1.... Normally closed [NC].
0
Output Terminal and related Function
C13 Alarm Relay output setting
X
Select function for Alarmrelay output
0... RUN(Run signal)
1.... FA1(Frequency arrival signal: command arrival)
2.... FA2(Frequency arrival signal: setting frequency or
more)
3.... OL(Overload advance notice signal)
4.... OD(Output deviation for PID control)
5.... AL(Alarm signal)
5
C14
Intelligentterminal Relay
output setting(RN0-RN1)
X
Select function for terminal RN0-RN1
0... RUN(Run signal)
1.... FA1(Frequency arrival signal: command arrival)
2.... FA2(Frequency arrival signal: setting frequency or
more)
3.... OL(Overload advance notice signal)
4.... OD(Output deviation for PID control)
5.... AL(Alarm signal)
1
C15
Intelligentterminal Relay
output setting(RN2-RN3)
X
Select function for terminal RN2-RN3
0... RUN(Run signal)
1.... FA1(Frequency arrival signal: command arrival)
2.... FA2(Frequency arrival signal: setting frequency or
more)
3.... OL(Overload advance notice signal)
4.... OD(Output deviation for PID control)
5.... AL(Alarm signal)
0
C16
Output Terminal RN0-RN1
a/b contact setting
X
Select logic convention, two option codes:
0.... a contact(normally open) [NO]
1.... b contact(normally closed) [NC]
0