background image

N700E INSTRUCTION MANUAL 

 

 

 

 

5-28 

 

 

Alarm Signal output [AL]

 

 

The Inverter alarm signal is active when a fault has occurred and it is in the Trip Mode.     
When the fault is cleared the alarm signal becomes inactive.   
We must make a distinction between the alarm signal [AL] and the alarm relaycontacts AL0, AL1and AL2. 
The signal [AL] is a logic function which you can assign to the relay output terminalRN0-RN1 and RN2-RN3. 
The most common (and default) use of the relay is for [AL], thus the labelingof its terminals. 

 
 

Option 

Code 

Terminal 

Symbol 

Function Name 

Input 

State 

Description 

AL 

Alarm signal 

ON 

When an alarm signal has occurred and has   
not been cleared 

OFF 

When no alarm has occurred since the last clearing 
of alarm(s) 

Valid for inputs: 

C13, C14, C15, C16, C17 

 
 
 
 

 

Required setting 

Notes: 
 
•When the alarm output is set to normally closed   

[NC], a time delay occurs until the contact is closed 
when the power is turned on.   
Therefore, when the alarm contact output is to be 
used, set a delay of about 2seconds when the 
power is turned on. 
Terminals RN0-RN1 and RN2-RN3 are relay 
outputs, so the electric specification of   
[AL] is similar tothe contact output terminals   
AL0, AL1, AL2. 

•See the description of AL1, AL2 and AL0. 
•When the inverter power supply is turned off,   

the alarm signal output is valid as long as   
the external control circuit has power. 

•The signal output has the delay time 

(300ms nominal) from the fault alarm output.   

•Output terminal RN0-RN1 is a relay contact a. 
  In case of contact b, setup C16. 
•Output terminal RN1-RN2 is a relay contact a. 
  In case of contact b, setup C17. 

 

 

Содержание N700E-055HF

Страница 1: ...N700E INSTRUCTION MANUAL A N700E INSTRUCTION MANUAL DOC NO HHIS WZ PE 082 010...

Страница 2: ...F TYPEMAXIMUM BRANCH CIRCUIT SHORT CIRCUIT PROTECTION SHALL BE PROVIDE BY FUSE ONLY 1 see each Model for exact kA 5KA N700E 055LF 075LFP N700E 370HF 450HFP All Model 10KA N700E 450HF 550HFP N700E 1320...

Страница 3: ...NOT AVOIDED CAN RESULT IN SERIOUS INJURY OR DEATH CAUTION INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH IF NOT AVOIDED CAN RESULT IN MINOR TO MODERATE INJURY OR SERIOUS DAMAGE OF PRODUCT THE MATTE...

Страница 4: ...IS NOT DESIGNED TO PROTECT PERSONAL INJURY CAUTION HEAVY OBJECT TO AVOID MUSCLE STRAIN OR BACK INJURY USE LIFTING AIDS AND PROPER LIFTING TECHNIQUES WHEN REMOVING OR REPLACING CAUTION THESE INSTRUCTIO...

Страница 5: ...2 TYPICAL CONSTRUCTIONS THAT REDUCE THE POSSIBILITY OF CONDUCTIVE POLLUTION ARE 1 THE USE OF AN UNVENTILATED ENCLOSURE 2 THE USE OF A FILTERED VENTILATED ENCLOSURE WHEN THE VENTILATION IS FAN FORCED...

Страница 6: ...4 OR LESS d VOLTAGE DISTORTION THD 10 OR LESS 2 INSTALLATION MEASURE a USE A FILTER DESIGNED FOR N700E INVERTER 3 WIRING a SHIELDED WIRE SCREENED CABLE IS REQUIRED FOR MOTOR WIRING AND THE LENGTH MUS...

Страница 7: ...ING INTO A CABINET OR BY ADDING COVERS AS FOLLOWS 1 CABINET AND COVER THE INVERTER MUST BE INSTALLED INTO A CABINET WHICH HAS THE PROTECTION DEGREE OF TYPE IP2X IN ADDITION THE TOP SURFACES OF CABINET...

Страница 8: ...10 6 N700E 110LF 150LFP 26 6 6 13 N700E 150LF 185LFP 26 6 4 13 N700E 185LF 220LFP 35 4 3 17 N700E 220LF 35 4 1 17 N700E 055HF 075HFP 12 4 12 10 6 N700E 075HF 110HFP 12 4 10 10 6 N700E 110HF 150HFP 12...

Страница 9: ...150LFP 60 N700E 150LF 185LFP 80 N700E 185LF 220LFP 100 N700E 220LF 125 N700E 055HF 075HFP 15 N700E 075HF 110HFP 20 N700E 110HF 150HFP 30 N700E 150HF 185HFP 40 N700E 185HF 220HFP 50 N700E 220HF 300HFP...

Страница 10: ...H IF NOT AVOIDED CAN RESULT IN SERIOUS INJURY OR DEATH INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH IF NOT AVOIDED CAN RESULT IN MINOR TO MODERATE INJURY OR SERIOUS DAMAGE TO THE PRODUCT THE SITU...

Страница 11: ...ording to the specifications in the text Chapter 6 Specifications Otherwise it may fall and there is a danger of injury l Be sure to install the unit on a perpendicular wall which is not subject to vi...

Страница 12: ...re l Be sure not to connect AC power supply to the output terminals U V W Otherwise there is a danger of injury and or fire and or damage to unit l Be sure not to connect a resistor to the DC terminal...

Страница 13: ...ger of injury l Be sure not to select retry mode for equipment running up and down or traversing because there is output free running mode in term of retry Otherwise there is a danger of injury and or...

Страница 14: ...eration or deceleration Were the RPM and frequency motor correct Were there any abnormal motor vibrations or noises Otherwise there is a danger of machine breakage l The AC reactor must be installed W...

Страница 15: ...3 3 3 1 3 Operation setting and frequency setting from both the digital operator and the terminal operator 3 3 3 2 Test Run 3 4 3 2 1 To input the operation setting and the frequency setting from the...

Страница 16: ...1 8 1 General Precautions and Notes 8 1 8 2 Inspection Items 8 1 8 3 General Inverter Electrical Measurements 8 4 9 RS485 Communication 9 1 10 Specification 10 1 10 1 Standard specification list 10 1...

Страница 17: ...one operation manual for the inverter 2 Make sure that there was no damage broken parts in the body during transportation of the unit 3 Make sure that the product is the one you ordered by checking t...

Страница 18: ...use as directed in this manual or attempted repair by unauthorized personnel Any damage sustained other than from transportation Which should be reported immediately Using the unit beyond the limits...

Страница 19: ...TRUCTION MANUAL 1 3 1 3 Appearance 1 3 1 N700E 055LF 075LFP N700E 220HF 300HFP Fig1 3 Appearance from the front Fig1 4 Front cover removed Front Cover Main circuit terminals Control circuit terminals...

Страница 20: ...700E INSTRUCTION MANUAL 1 4 1 3 2 N700E 300HF 370HFP N700E 1320HF 1600HFP Fig1 5Appearance from the front Fig1 6Front cover removed Front Cover Main circuit terminals Control circuit terminals Operato...

Страница 21: ...TION MANUAL 1 3 3 N700E 1600HF 2000HFP N700E Operator Front Cover Control circuit terminals Main circuit terminals 1 5 1600HF 2000HFP N700E 2200HF 2500HFP Fig1 7Appearance from the front Fig1 8Front c...

Страница 22: ...TION MANUAL 1 3 4 N700E 2800HF 3200HFP N700E Operator Front Cover Control circuit terminals Main Circuit Terminals 1 6 2800HF 3200HFP N700E 3500HF 3800HFP Fig1 9Appearance from the front Fig1 10Front...

Страница 23: ...rter in a place which can bear the weight according to the specifications in the text Otherwise it may fall and result in possible injury l Be sure to install the unit on a perpendicular wall which is...

Страница 24: ...er should not exceed the allowable temperature range 14 to 122 F 10 to 50 The temperature should be measured in the air gap surrounding the inverter shown in the diagram above If the temperature excee...

Страница 25: ...hese positions are wrong airflow around the inverter decreases and the temperature surrounding the inverter will rise So please make sure that the temperature around is within the limit of the allowab...

Страница 26: ...ree phase only inverter with single phase power Otherwise there is a danger of fire l Be sure not to connect AC power supply to the output terminals U V W Otherwise there is a danger of injury and or...

Страница 27: ...N700E INSTRUCTION MANUAL 2 5 2 2 1 Terminal Connection Diagram sink type Fig 2 3 Terminal Connection Diagram sink type...

Страница 28: ...run command FW Reverse runcommand RV multi speed commands1 4 CF1 4 2 stage accel decel 2CH Reset RS Terminal software lock SFT Unattended start protection USP Current input selection AT Jogging operat...

Страница 29: ...oad 0 2A inductor load DC 30V 3 0A resistor load 0 7A inductor load RN2 RN3 Intelligent Output signal AL0 AL1 AL2 Alarm output terminal Run status signal RUN Frequency arrival signal FA1 Set frequency...

Страница 30: ...s of the capacity of inverter and case beyond 500kVA A drastic change in the power supply Example Turning on off of the power supply should not be done more than three times in one minute It has the p...

Страница 31: ...terminals P N on the inverter l The braking resistor is then wired into the External Braking unit and not directly to the Inverter l The cable length should be less than 5 meters and twist the connec...

Страница 32: ...3 G G N700E 110LF 150LFP M5 13 R L1 S L2 T L3 PD 1 P RB U T1 V T2 W T3 G G N700E 150LF 185LFP N700E 150HF 185HFP N700E 185HF 220HFP N700E 220HF 300HFP M5 13 R L1 S L2 T L3 PD 1 P RB U T1 V T2 W T3 G G...

Страница 33: ...1 PD 1 P N R L1 S L2 T L3 U T1 V T2 W T3 G G N700E 1600HF 2000HFP N700E 2200HF 2500HFP M10 38 PD 1 P N R L1 S L2 T L3 U T1 V T2 W T3 G G N700E 2800HF 3200HFP N700E 3500HF 3800HFP M13 38 Table 2 3Wirin...

Страница 34: ...noise filter zero phase reactor Using the inverter may cause noise on the peripheral radio through the power lines This part reduces noise 4 Input radio noise filter capacitor filter This part reduce...

Страница 35: ...5HFP More than 8 6 M5 3 0 UCB100R 50A HiMC40 18 5 N700E 185HF 220HFP More than 8 6 M5 3 0 UCB100R 75A HiMC40 22 N700E 220HF 300HFP More than 6 6 M5 3 0 UCB100R 75A HiMC50 30 N700E 300HF 370HFP More th...

Страница 36: ...22 N700E 185HF 220HFP More than 8 6 M5 3 0 UCB100R 75A HiMC50 30 N700E 220HF 300HFP More than 6 M6 4 5 UCB100R 100A HiMC65 37 N700E 300HF 370HFP More than 4 M6 4 5 UCB250S 100A HiMC80 45 N700E 370HF 4...

Страница 37: ...l circuit terminals Connect the screened cable to the common terminal Limit the connection wires to 65 feet Separate the control circuit wiring from the main power and relay control wiring When using...

Страница 38: ...nal 24Vdc The connection to the input programmable logic controller sequencer Source Mode Internal power supply Source Mode External power supply Sink Mode Internal power supply Sink Mode External pow...

Страница 39: ...nication is for purpose of preventingthe distortionand attenuationof the communication line and this resistor means the Impedance matching resistor in long distance transport of RS 485 Data The termin...

Страница 40: ...danger of injury l Be sure not to select retry mode for up and down equipment or traveling equipment because there is an output free running mode in term of retry Otherwise there is a danger of injur...

Страница 41: ...it after checking the tolerance of the motor and machine Otherwise there is a danger of injury l Install an external breaking system if needed Otherwise there is a danger of injury l If a motor is op...

Страница 42: ...setting and the current setting Both are selective The control circuit terminal list shows necessary things for each setting The operation setting switch relay etc The frequency setting signals from...

Страница 43: ...es are shown Set 1 Terminal with UP DOWN key press the STR key once to set the operation setting for the operator Indication code turns back to A01 4 Set terminal with the operation setting selection...

Страница 44: ...peration setting selection Set A02 as the indication code press the FUNC key once Set 2 OPE with UP DOWN key press the STR key once to set the operation setting for the operator Indication code turns...

Страница 45: ...m history and setting value RUN Key Press this key to run the motor The Run enable LED must be terminal operation STOP RESET Key This key is used for stopping the motor or resetting errors When either...

Страница 46: ...N700E INSTRUCTION MANUAL 4 2 Key Description in RPM...

Страница 47: ...INSTRUCTION MANUAL 4 3 Extended function mode navigation map Display description When the inverter is turned on one of the display group can appear according to the setting value of b30 display code s...

Страница 48: ...play digit movement Press the UP key and DOWN key at the same time in data setting mode Change Scroll mode to Shift mode 2 Data setting method Stop in target group using UP DOWN key Press the function...

Страница 49: ...direction monitor Three different indications F Forward Run Stop r Reverse Run d05 PID feedback monitor Displays the scaled PID process variable feedback value A50 is scale factor d06 Intelligent inpu...

Страница 50: ...alarm event press the UP DOWN key Output current at alarm event press the UP DOWN key DC link voltage at alarm event press the FUNC key d13 display No trip event d14 Trip history 1 monitor Displays t...

Страница 51: ...potentiometer can be monitored 0 00Hz F02 Acceleration time1 setting O 0 1 3000sec 0 1 999 9 by 0 1sec 1000 3000 by 1sec Minimum setting range 30 0sec F03 Deceleration time 1 setting O 0 1 3000sec 0 1...

Страница 52: ...ency setting X Settable from the base frequency A03 up to 400Hz in units of 0 01 Hz In the case of sensorless vector control possible for driving to 300Hz 60 00Hz Analog Input Settings A05 External fr...

Страница 53: ...z speed5 30Hz speed6 40Hz speed7 50Hz speed8 60Hz etc 0Hz A26 Jogging frequencysetting O Defines limited speed for jog range is 0 5 to 10 00Hz in units of 0 01Hz The jogging frequency is provided safe...

Страница 54: ...Injection Braking Settings A33 DC injection braking function selection X Sets two options for DC injection braking 0 Disable 1 Enable 0 A34 DC injection brakingfrequencysetting X The frequency at whic...

Страница 55: ...g X Sets a limit on output frequency greater than zero Range is 0 00 to frequency upper limit A38 in units of 0 01Hz 0 00Hz A40 A42 A44 Jump center frequency setting X Up to 3 output frequencies can b...

Страница 56: ...O Duration of 2nd segment of acceleration range is 0 1 to 3000 sec Second acceleration can be set by the 2CH terminal input or frequency transition setting 30 0sec A55 Second deceleration time settin...

Страница 57: ...input signal adjustment Range is 10 0 to 10 0 0 0 A62 Input voltage Gain setting O Set the voltage gain for external analog signal input signal adjustment Range is 0 0 to 200 0 100 0 A63 Input current...

Страница 58: ...tage input 0 A74 PID P gain O Sets the proportional gain that is applied to the deviation between the reference and the feedback signal 0 1 to 1000 in units of 0 1 100 0 A75 PID I gain O Set the integ...

Страница 59: ...of pressure within a fixed value Input method of target value signal and feedback signal Set the reference signal according to the PID reference setting method A72 Set the feedback signal according to...

Страница 60: ...put 3 Remote 2 Keypad 0 Potentiometer 1 Analog input A77 PID error limit CurFreq PrePID Freq LIMIT A73 PID Feed back source C01 C06 22 PIDIR A82 PrePID Freq GAIN 2 PID enable F F LIMIT F02 Acceleratio...

Страница 61: ...ID Note 6 Sleep and Wake up In Function code A83 Sleep Frequency the sleep function is activated When the output frequency falls below the Sleep Frequency A83 for the Sleep Delay Time A84 operates the...

Страница 62: ...tripping the power failure alarm Range is 0 3 to 1 0sec If under voltage exists longer than this time the inverter trips even if the restart mode is selected This function are depends on the machine...

Страница 63: ...inverter setting range 0 2x inverter rated current 2 0x inverter rated current HD 180 ND 150 132kW HD 150 ND 120 160kW b08 Overload restriction constant setting X Set the deceleration rate when invert...

Страница 64: ...rsion factor setting O Specify a constant to scale the displayed RPM for d08 monitor range is 0 01 to 99 99 in units of 0 01 1 00 b15 STOP key validity during terminal operation X Select whether the S...

Страница 65: ...frequency of the inverter can be selected as follows 0 0Hz Starting operation 1 Frequency matching start operation 0 b24 Failure status output selection by relay in case of failure O In case of low vo...

Страница 66: ...ed 0 No detect time out 0 60 Detect time out when communication cut off Unit second 0 b29 Communication time out operation mode O Set the communication time out operation mode 0 Always active 1 Active...

Страница 67: ...0kHz N700E 1600HF 2000HFP 3500HF 3800HFP 2 0kHz 2 0kHz By setting up b26 1 All models have the same carrier frequency2 0kHz Note8 Carrier frequency ranges of different inverter types Model Range kHz N...

Страница 68: ...on after frequency matching The VFD may attempt to restart itself up to 3 times in frequency matching mode after auto restart attempts When the restart counter reaches 4 times the operation stops and...

Страница 69: ...restart itself up to 10 times in frequency matching mode after auto restart attempts When the restart counter reaches 11 times the operation stops and the alarm relay has the inactive operation The VF...

Страница 70: ...SFT 13 Analog input current voltage selection signal AT 14 Reset RS 15 Start STA 16 Keep STP 17 Forward reverse F R 18 Remote control UP UP 19 Remote control DOWN DOWN 20 Local Keypad Operation O R 21...

Страница 71: ...0 Output Terminal and related Function C13 Alarm Relay output setting X Select function for Alarmrelay output 0 RUN Run signal 1 FA1 Frequency arrival signal command arrival 2 FA2 Frequency arrival si...

Страница 72: ...1 Overload advance notice signallevel setting X Sets the overload signal level between 10 and 200 resolution is 0 1 0 1x Inverter rated current 2 0x Inverter rated current 100 0 C22 Acceleration arriv...

Страница 73: ...selection X Select function for terminal FM 3 options 0 output frequency monitor 1 output current monitor 2 output voltage monitor 3 output power monitor 1 C26 AMI gain adjustment O Range is 0 to 250...

Страница 74: ...7 5kW 11H 380V 11kW 15H 380V 15kW 18 5H 380V 18 5kW 22H 380V 22kW 30H 380V 30kW 37H 380V 37kW 45H 380V 45kW 55H 380V 55kW 75H 380V 75kW 90H 380V 90kW 110H 380V 110kW 132H 380V 132kW 160H 380V 160kW 2...

Страница 75: ...inverter stops the output and the motor enters the free run state coasting EXT 10 External trip It is possible to enter the external trip state USP 11 Unattended start prevention Restart prevention wh...

Страница 76: ...to code C01 C06 AT signal OFF It is possible to command frequency using voltage signal terminal O L 0 10V AT signal ON It is possible to command frequency using current signal terminal OI L 4 20mA Whe...

Страница 77: ...rter alarm signal is active when a fault has occurred Output terminal AL0 AL1 AL2 RUN 0 Run signal When the RUN signal is selected the inverter outputs a signal on that terminal when it is in the RUN...

Страница 78: ...indicator so that it cannot be used as a line speed signal The indicator accuracy after adjustment is about 5 Depending on the meter the accuracy may exceed this value 2 output current monitor signal...

Страница 79: ...not be used as a line speed signal The indicator accuracy after adjustment is about 5 Depending on the meter the accuracy may exceed this value 2 output current monitor signal The AMI output varies wi...

Страница 80: ...in Run Mode motor stop 1 RV Reverse Run Stop ON Inverter is in Run Mode motorruns reverse OFF Inverter is in Run Mode motorruns stop Valid for inputs Required setting C01 C02 C03 C04 C05 C06 Example A...

Страница 81: ...if you need eight or less speeds Note When choosing a subset of speeds to use always start at the top of the table and with the least significant bit CF1 CF2 etc Multi speed Control circuit terminal...

Страница 82: ...FF ON OFF ON Speed 3 A13 OFF OFF ON ON ON Speed 4 A14 OFF ON OFF OFF ON Speed 5 A15 OFF ON OFF ON ON Speed 6 A16 OFF ON ON OFF ON Speed 7 A17 OFF ON ON ON ON Speed 8 A18 ON OFF OFF OFF ON Speed 9 A19...

Страница 83: ...n monitor the current frequency with monitor functionF01 during each segment of a multispeed operation There are two ways to program the speeds into the registersA20 to A25 Programming using the CF sw...

Страница 84: ...z or less to prevent tripping The type of deceleration used to end a motor jog is selectable by programming function A27 The options are 0 Free run stop coasting 1 Deceleration normal level and stop 2...

Страница 85: ...ion ramp we recommend setting the jogging frequency in A26 to 5Hz or less to prevent tripping stop Run command frame construction Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 Reserved JOG RST REV FWD Examp...

Страница 86: ...eceleration time2 to set the second stage acceleration and deceleration time In the graph shown above the 2CH becomes active during the initial acceleration This causes the inverter to switch form usi...

Страница 87: ...eed right graph when the FRS terminal turns off The application determines which is the best setting Parameter B03 specifies a delay time before resuming operation from a free run stop To disable this...

Страница 88: ...e trip state You must reset the inverter or cycle power to clear the error returning the inverter to the Stop Mode Option Code Terminal Symbol Function Name Input State Description 10 EXT External Tri...

Страница 89: ...turning off the Run command Then the Run command can turn on again and start the inverter output Option Code Terminal Symbol Function Name Input State Description 11 USP Unattended startProtection ON...

Страница 90: ...Terminal Symbol Function Name Input State Description 12 SFT Software Lock ON The keypad and remote programming devices are prevented from changing parameters OFF The parameters may be edited and sto...

Страница 91: ...nal Symbol Function Name Input State Description 13 AT Analog Input Voltage current select ON Terminal OI is enabled for current input uses terminal L for power supply return OFF Terminal O is enabled...

Страница 92: ...it exists and power up reset is applied OFF Normal power on operation Valid for inputs C01 C02 C03 C04 C05 C06 Example Required setting none Notes When the control terminal RS input is already at powe...

Страница 93: ...ction ON Don t care OFF Stop Active low Level triggered 17 F R 3 Wire input function ON While motor runs and F R terminal is keeping high state then it will change motor running direction to REVERSE O...

Страница 94: ...is ON Option Code Terminal Symbol Function Name Input State Description 18 UP UP Function ON Accelerating motor from present frequency Output frequency increases OFF Motor output acts normally 19 DOW...

Страница 95: ...ommand is changed to the control terminal input like as A01 1 and Run command is changed to the control terminal input like as A02 1 OFF Frequency command is changed to the A01 setting method and Run...

Страница 96: ...et Option Code Terminal Symbol Function Name Input State Description 22 PIDIR PID Integral Reset ON The accumulated Integral term of the PID controller is reset to zero OFF Normal power on operation V...

Страница 97: ...verter operates with PID control Option Code Terminal Symbol Function Name Input State Description 23 PIDD PID Disable ON PID controller is off PID Disable OFF PID controller is on PID Enable Valid fo...

Страница 98: ...rter output frequency when itturns on Output terminal RN0 RN1 is a relay In case of contact b setup C16 Output terminal RN1 RN2 is a relay In case of contact b setup C17 5 24 output terminals When the...

Страница 99: ...rossed Option Code Terminal Symbol Function Name Input State Description 1 FA1 Frequencyarrival type 1signal ON when output to motor is at the set frequency OFF when output to motor is off or in any a...

Страница 100: ...dvance notice signal ON when output current is more than the set threshold for the overload signal OFF when output current is less than the set threshold for the overload signal Valid for inputs C13 C...

Страница 101: ...ut State Description 4 OD Output deviation for PID control ON When PID error is more than theset threshold for the deviation signal OFF When PID error is less than the set threshold for the deviation...

Страница 102: ...ince the last clearing of alarm s Valid for inputs C13 C14 C15 C16 C17 Required setting 5 Notes When the alarm output is set to normally closed NC a time delay occurs until the contact is closed when...

Страница 103: ...n or Stop Mode The relay contacts switch to the opposite position when it is Trip Modeor when input power is off Contact a Initial setting During normal runningor power is turned off When an alarm occ...

Страница 104: ...uired torque characteristic or speed control characteristic may not bemaintained in case that the inverter capacity is more than twice the capacity of the motor in use Function setting method Select t...

Страница 105: ...W 3 7H 380V 3 7kW 5 5L 220V 5 5kW 5 5H 380V 5 5kW 7 5L 220V 7 5kW 7 5H 380V 7 5kW 11L 220V 11kW 11H 380V 11kW 15L 220V 15kW 15H 380V 15kW 18 5L 220V 18 5kW18 5H 380V 18 5kW 22L 220V 22kW 22H 380V 22kW...

Страница 106: ...on no rotation Single phase excitation End display Auto tuning process completed Auto tuning process failed Note 1 The motor parameter of N700E is standard data of HYUNDAI standard 4 poles motor At th...

Страница 107: ...11kW 15H 380V 15kW 18 5H 380V 18 5kW 22H 380V 22kW 30H 380V 30kW 37H 380V 37kW 45H 380V 45kW 55H 380V 55kW 75H 380V 75kW 90H 380V 90kW 110H 380V 110kW 132H 380V 132kW 160H 380V 160kW 200H 380V 200kW 2...

Страница 108: ...ating torque When low frequency a few Hz torque is insufficient Slowly increase the motor constantR1 in relation to auto tuning data within 1 to 1 2 times R1 H08 H10 Slowly increase the motor no load...

Страница 109: ...t circuited This condition causes excessive current for the inverter sothe inverter output is turned off E04 or E34 USP error The USP error is indicated when the power is turned on with the Inverterin...

Страница 110: ...of history isprocessing There is no data available Trip history PID feedback data The auto tuning operation terminates normally 6 2 Contents Display It is displayed when initialization of data is proc...

Страница 111: ...command s Inverter outputs U V W are supplying voltage Is the motor load too heavy Is the motor locked Reduce load and test the motor independently The direction of the motoris reversed Are the conne...

Страница 112: ...g will not change Run Stop does not operate Was the standard operatormode and terminal modechanged correctly Make sure the setting mode of A01 A02 is changed Truefor all parameters If you re using the...

Страница 113: ...f fire due to wire breakage and or injury to personnel 8 2 Inspection Items 1 Daily inspection 2 Periodic inspection approximately once a year 3 Insulation resistance test approximately once two years...

Страница 114: ...which include Spare parts Part description Symbol Quantity Note Used Spare Cooling FAN FAN 2 2 5 5KW HD 55KW HD 7 5KW ND 75KW ND 3 3 75KW HD 132KW HD 90KW ND 160KW ND 4 4 160KW HD 220KW HD 200KW ND 25...

Страница 115: ...2 0 2 5Nm M6 2 5 3 0Nm M8 15 2 21 5Nm M10 28 0 33 0Nm M12 39 0 50 0Nm Components Overheating Thermaltrip events No trip events Housing Dirt dust Visual Vacuum dust and dirt Terminal block Secure conne...

Страница 116: ...R S T Power Supply U V W R S T U V W I N V E R T E R Motor Circuit location of measurement Measuring instrument Notes Moving coil type voltmeter or rectifier type voltmeter Fundamental wave effective...

Страница 117: ...mmunication code Data bits Parity Stop bit Starting method Wait time Connection type Error check RS485 Half duplex 9600 Binary code 8 No 1 External request 10 1000ms 1 N Max32 Frame CRC CMD MAXREQ par...

Страница 118: ...ommunication number 1 byte 1 32 Command Frame type 1 byte 0x03 Parameter Parameter 2 byte 1 st byte Group 2 nd byte Index Note1 Parameter number Request parameter number 2 byte 1 st byte 0x00 2 nd byt...

Страница 119: ...ata 2 byte Setting value Note 2 CRC Hi 1 byte Higher 8bit of 16bit CRC CRC Lo 1 byte Lower 8bit of 16bit CRC Inverter response frame Communication number Order Parameter Data CRC Hi CRC Lo Description...

Страница 120: ...put current DC link voltage at trip occurs Trip Information Previous first trip Previous second trip Previous third trip Trip count 1 st byte 0x01 0x01 0x01 0x01 0x01 2 nd byte 0x0D 0x11 0x15 0x19 0x1...

Страница 121: ...0 1 st byte 0x00 2 nd byte 0x64 Note3 Special parameter Run command Parameter 1 st byte 0x00 2 nd byte 0x02 setting data 1 st byte Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 Reserved 2 nd byte Bit7 Bit6...

Страница 122: ...0x00 0x01 The sequence of addition Byte 01x01 16 BIT REGISTER MSB Flag Exclusive OR 1111 1111 1111 1111 01 0000 0001 1111 1111 1111 1110 Shift 1 0111 1111 1111 1111 Shift 2 0011 1111 1111 1111 1 Poly...

Страница 123: ...5 11 15 18 5 22 ND 7 5 11 15 18 5 22 30 Rated capacity kVA HD 380V 7 9 10 5 15 1 21 1 25 0 29 6 480V 10 0 13 3 19 1 26 6 31 6 37 4 ND 380V 10 4 15 2 20 0 25 6 29 7 39 4 480V 12 5 18 2 24 1 30 7 35 7...

Страница 124: ...l model Control system Note3 Space vector modulation PWM system Output frequency range Note4 0 01 400Hz Frequency accuracy Note5 Digital command 0 01 for Max frequency analog frequency 0 1 25 10 Frequ...

Страница 125: ...Standard specification Ambient temperature 10 40 If ambient temperature is above 40 Carrier frequency should be lower than default value Storage temperature 20 60 Ambient humidity Below 90 RH Install...

Страница 126: ...use Additional braking unit should be installedfor above Recommended DB Resistors for the Rated Inverter Capacity 5 ED 1 Inverter capacity Ohm Wattage W 2 055LF 075LFP 17 1000 075LF 110LFP 17 1000 11...

Страница 127: ...P N700E 075LF 110LFP N700E 110LF 150LFP N700E 055HF 075HFP N700E 075HF 110HFP and N700E 110HF 150HFP model external dimension mm 2 N700E 150LF 185LFP N700E 185LF 220LFP N700E 220LF N700E 150HF 185HFP...

Страница 128: ...N700E INSTRUCTION MANUAL 10 6 3 N700E 300HF 370HFP N700E 370HF 450HFPmodel external dimension mm 312 W 265 W1 4 10 240 W2 2 10 265 4 N700E 450HF 550HFP N700E 550HF 750HFPmodel external dimension mm...

Страница 129: ...N700E INSTRUCTION MANUAL 10 7 5 N700E 750HF 900HFP N700E 900HF 1100HFPmodel external dimension mm 6 N700E 1100HF 1320HFP N700E 1320HF 1600HFPmodel external dimension mm...

Страница 130: ...0E INSTRUCTION MANUAL 10 8 7 N700E 1600HF 2000HFP N700E 2200HF 2500HFPmodel external dimension mm 8 N700E 2800HF 3200HFP N700E 3500HF 3800HFPmodel external dimension mm 3 14 395 D 806 W 3 14 700 W1 53...

Страница 131: ...00E 150HF 185HFP 250 229 390 376 188 7 7 N700E 185HF 220HFP 250 229 390 376 188 7 7 N700E 220HF 300HFP 250 229 390 376 188 7 7 5 N700E 300HF 300HFP 312 265 240 530 510 270 10 22 N700E 370HF 450HFP 312...

Страница 132: ...rawing changed 12 03 HHIS WZ PE 082 02 4 B Group function code changed 12 05 HHIS WZ PE 082 03 5 B Group function code b02 changed 12 06 HHIS WZ PE 082 04 6 Fuse table changed 12 10 HHIS WZ PE 082 05...

Отзывы: