N700E INSTRUCTION MANUAL
4-12
Func-
code
Name
Run-
time
Edit
Description
Defaults
Automatic Voltage Regulation (AVR) Function
A52 AVR function selection
X
Automatic (output) voltage regulation,
selects from three type of AVR functions
three option codes:
0... Constant ON
1... Constant OFF
2... OFF during deceleration
The AVR feature keeps the inverter
output waveform at a relatively constant
amplitude during power input fluctuations
2
A53 Motor inputvoltage setting
X
200V class inverter settings:
.... 200/220/230/240
400V class inverter settings:
.... 380/400/415/440/460/480
LF Model
220V
HF Model
(Note3)
Second Acceleration and Deceleration Functions
A54
Second acceleration time
setting
O
Duration of 2nd segment of acceleration, range is
0.1 to 3000 sec.
Second acceleration can be set by the [2CH] terminal
input or frequency transition setting
30.0sec
A55
Second deceleration time
setting
O
Duration of 2nd segment of deceleration, motor range
is 0.1 to 3000 sec.
Second acceleration can be set by the
[2CH] terminal input or frequency
transition setting
30.0sec
A56
Two stageacce1/dece1
switching methodselection
X
Two options for switching from 1st to 2nd
accel/decel:
0.... 2CH input from terminal
1.... transition frequency
0
A57
Acc1 to Acc2frequency
transition point
X
Output frequency at which Accel 1 switches to Accel
2, range is 0.00 to maximum frequency(A04) in units
of 0.01Hz.
0.00Hz
A58
Decel 1 to Decel 2
frequency
transition point
X
Output frequency at which Decel 1 switches to Decel
2, range is 0.00 to maximum frequency(A04) in units
of 0.01Hz.
0.00Hz