N700E INSTRUCTION MANUAL
2-13
(4) Common applicable tools
Class
Motor
Output
(kW)
Inverter
model
Power lines
R,S,T
U,V,W,
P,PD,N
(
AWG,kcmil
)
External
resister
between
P and
RB
(
AWG
)
Screw
size
of
Terminal
Torque
(N•m)
Applicable Tools
Leak breaker
(MCCB)
Electro-
magnetic
Controller
(MC)
200V
Class
5.5
N700E-
055LF/075LFP
More than8
8
M4
1.2
UCB100R
50A
HiMC32
7.5
N700E-
075LF/110LFP
More than 8
8
M4
1.2
UCB100R
50A
HiMC32
11
N700E-
110LF/150LFP
More than 6
8
M5
3.0
UCB100R
75A
HiMC50
15
N700E-
150LF/185LFP
More than 4
4
M5
3.0
UCB100R
100A
HiMC65
18.5
N700E-
185LF/220LFP
More than 3
4
M6
4.5
UCB250S
150A
HiMC80
22
N700E-220LF
More than 1
4
M6
4.5
UCB250S
150A
HiMC110
400V
Class
5.5
N700E-
055HF/075HFP
More than12
10
M4
1.2
UCB30C
30A
HiMC18
7.5
N700E-
075HF/110HFP
More than10
10
M4
1.2
UCB30C
30A
HiMC18
11
N700E-
110HF/150HFP
More than8
8
M4
1.2
UCB100R
50A
HiMC32
15
N700E-
150HF/185HFP
More than 8
6
M5
3.0
UCB100R
50A
HiMC40
18.5
N700E-
185HF/220HFP
More than 8
6
M5
3.0
UCB100R
75A
HiMC40
22
N700E-
220HF/300HFP
More than 6
6
M5
3.0
UCB100R
75A
HiMC50
30
N700E-
300HF/370HFP
More than 4
-
M6
4.5
UCB100R
100A
HiMC65
37
N700E-
370HF/450HFP
More than 2
-
M6
4.5
UCB250S
100A
HiMC80
45
N700E-
450HF/550HFP
More than 1
-
M8
6.0
UCB250S
150A
HiMC110
55
N700E-
550HF/750HFP
More than
2/0
-
M8
6.0
UCB250S
175A
HiMC130
75
N700E-
750HF/900HFP
More than
4/0
-
M8
6.0
UCB400S
250A
HiMC180
90
N700E-
900HF/1100HFP
More than
300(kcmil)
-
M8
6.0
UCB400S
250A
HiMC220
110
N700E-
1100HF/1320HFP
More than
350(kcmil)
-
M10
10.0
UCB400S
350A
HiMC260
132
N700E-
1320HF/1600HFP
More than
400(kcmil)
-
M10
10.0
UCB400S
350A
HiMC300
160
N700E-
1600HF/2000HFP
More than
4/0*2P
-
M10
10.0
UCB800S
700A
HiMC400
220
N700E-
2200HF/2500HFP
More than
300
(kcmil)*2P
-
M10
10.0
UCB800S
800A
HiMC500
280
N700E-
2800HF/3200HFP
More than
4/0*4P
-
M10
10.0
UCB1000S 1000A
HiMC630
350
N700E-
3500HF/3800HFP
More than
300
(kcmil)*4P
-
M10
10.0
UCB1250S 1250A
HiMC800
Table 2-6Common applicable tools for N700E inverters(Heavy Duty)