N700E INSTRUCTION MANUAL
VII
UL WARNINGS AND CAUTIONS MANUAL FOR N700E SERIES
THIS AUXILIARY INSTRUCTION MANUAL SHOULD BE DELIVERED TO THE END USER.
1. WIRING MARKING FOR ELECTRICAL PRACTICE AND WIRE SPECIFICATIONS
“USE COPPER CONDUCTOR ONLY, 75
℃
WITH A TORQUE RATING.
2. TIGHTENING TORQUE AND WIRE RANGE
TIGHTENING TORQUE AND WIRE RANGE FOR FIELD WIRING TERMINALS ARE MARKED
ADJACENT TO THE TERMINAL OR ON THE WIRING DIAGRAM.
MODEL NAME
N700E-(Heavy Duty/Normal
Duty)
TIGHTENINGTORQUE
[LB-IN]
WIRE RANGE
(AWG)
RING
TERMINAL SIZE
MAXIMUM
WIDE [mm]
N700E-055LF/075LFP
12.4
8
10.6
N700E-075LF/110LFP
12.4
8
10.6
N700E-110LF/150LFP
26.6
6
13
N700E-150LF/185LFP
26.6
4
13
N700E-185LF/220LFP
35.4
3
17
N700E-220LF
35.4
1
17
N700E-055HF/075HFP
12.4
12
10.6
N700E-075HF/110HFP
12.4
10
10.6
N700E-110HF/150HFP
12.4
8
10.6
N700E-150HF/185HFP
26.6
8
13
N700E-185HF/220HFP
26.6
8
13
N700E-220HF/300HFP
26.6
6
13
N700E-300HF/370HFP
35.4
4
17
N700E-370HF/450HFP
35.4
2
17
N700E-450HF/550HFP
58.4
1
22
N700E-550HF/750HFP
58.4
2/0
22
N700E-750HF/900HFP
58.4
4/0
29
N700E-900HF/1100HFP
58.4
300 (kcmil)
29
N700E-1100HF/1320HFP
105.7
350 (kcmil)
30
N700E-1320HF/1600HFP
105.7
400 (kcmil)
30
N700E-1600HF/2000HFP
113
4/0*2P
38
N700E-2200HF/2500HFP
113
300 (kcmil)*2P
38
N700E-2800HF/3200HFP
113
4/0*4P
38
N700E-3500HF/3800HFP
113
300 (kcmil)*4P
38
*RECOMMENDED RING TERMINAL SIZE (UL LISTED) FOR 055LF~110LF:MAXIMUM WIDE 12mm