N700E INSTRUCTION MANUAL
4-19
Func-
code
Name
Run-
time
Edit
Description
Defaults
Overload Restriction
b06
Overload overvoltage
Restrictionmode selection
X
Select overload or overvoltage restrictionmodes
0.... Overload, overvoltage restriction modeOFF
1.... Only overload restriction mode ON
2.... Only overvoltage restriction mode ON
3.... Overload /overvoltage restriction mode ON
3
b07
Overload restrictionlevel
setting
X
Sets the level for overload restriction, between 20% and
200% of the rated current of the inverter,
setting range 0.2x(inverter rated current) ~
2.0x(inverter rated current)
HD : 180%
ND : 150%
(
≤
132kW)
HD : 150%
ND : 120%
(
≥
160kW)
b08
Overload restriction
constant setting
X
Set the deceleration rate when inverter detects
overload, range is 0.1 to 10.0 andresolution is 0.1
(b08)
(b07)
Motor
current
Output
frequency
1.0sec
Software Lock Mode
b09
Software lockmode
selection
X
Prevents parameter changes, in four
options, option codes:
0.... All parameters except b09 are locked
when SFT from terminal is on
1.... All parameters except b09 and out-
put frequency F01 are locked when
SFT from terminal is ON
2.... All parameters except b09 are locked
3.... All parameters except b09 and output
frequency F01 setting are locked
0