Page 56
»
Open pump (bayonet lock).
»
Remove all residue from the drain hoses and pump
(possibly replace o-ring (A)).
»
Assemble pump.
»
Moisten o-ring (C) and place in the side connection of
the base.
»
Push pump into the base and secure tightly with screws
(G).
»
Moisten o-ring (D) and place on the side connection of
the pump.
»
Slide union adapter (E) over the side connection of the
pump.
»
Connect electrical connector to the pump (polarity not
specified).
»
Open water supply.
»
Switch on unit and check for leaks after 15-30 minutes
of operation.
If leakage occurs, switch off power supply and repair the leaks,
following safety instructions for work on live components!
9.12
Removing Inlet Solenoid Valve and Clean-
ing Fine Mesh Filter
Removal
»
Close off water supply.
»
Drain steam cylinder (9) by setting main switch to Pos
II.
»
Disconnect power supply and secure against restart
(switch off control switch, remove main fuse and control
fuse F1).
»
Verify absence of electric current.