5.9
Chimney-compartment
Between electrical compartment (right side) and steam produc-
tion compartment (left side) the chimney compartment is
located. The chimney compartment is used to cool electronic
components. For proper function make sure that the three holes
in the top side of the housing are not covered - otherwise the
heat removal is too low and a thermal cutout could be triggered.
5.10
Unit Installation Check
Attention:
This unit may only be operated by qualified and prop-
erly trained personnel.
Please check the installation using the following list:
Does unit hang vertically?
Are wall distances to the unit within the range
Does steam hose have a slope of 5-10%?
Is condensate hose installed with a loop of min. 200
mm/7.9inch?
Is steam manifold positioned correctly?
Are all bolts and clamps tightened?
Is steam manifold installed horizontaly?
Are all sealings installed?
tAre the three holes in the top side of the housing not
covered?