Page 43
7.2
Cable Connections
The table below shows the cable connections provided in
HeaterLine steam humidifiers:
Characteristics of metric cable connections:
7.3
Control Connection
Warning:
Set the control to prevent overly frequent activation
and deactivation of the steam humidifier. Main contactors are
wearing parts and are guaranteed by the manufacturer for
150,000 cycles. Operation which minimizes activation cycles will
extend the life of the main contactors.
7.4
Safety Interlock
Note:
Install contact interlocks, i.e. max. hygrostat, vane relay,
pressure controller, air interlock etc. in series between Terminals
1 and 2.
Warning:
It is standard practice to install a max. hygrostat in the
safety interlock. The max. hygrostat acts as a safety device in
the event of a humidity sensor malfunction and protects against
overhumidification.
Unit
Connection
M16
Connection
M25
Connection
M32
HL6 - 45
4
2
1
Thread
across-flats
dimensions [mm]
for cable diameter
[mm]
M16x1,5
19
4,5 - 10
M25x1,5
30
9 - 17
M32x1,5
36
11 - 21
Содержание HeaterLine HL 12