Page 13
At the standard setting, the inlet solenoid valve (14) opens when
the water level remains below “humidification” level for 10 sec-
onds. The water level then rises again to “humidification” level.
For more information, also see section “Exploded View.”
The steam cylinder (9) is made of stainless steel. The cover (5)
is attached to the steam cylinder using a clamping ring (7). Up to
5 heater elements (8) are mounted on the cover.
The heater elements are equipped with a mechanical high tem-
perature safety. This mechanism provides a redundant safety
system in the event of excessively low water levels (“Dry Run”).
The cylinder water is periodically flushed out with a heavy-duty
blow-down pump (10). Hygromatik’s SUPER FLUSH system
effectively assists this operation. The SUPER FLUSH mecha-
nism generates a strong whirlpool effect in the strainer basket
which aids removal of scale deposits during the blow-down pro-
cess.
During this procedure, steam production is interrupted for
a few minutes.
Steam is fed into air-conditioning ducts through special steam
hoses and steam manifolds. Under normal conditions, this
steam has virtually no heating effect on the air to be humidified.
Accumulated condensate can be returned to the steam cylinder
via a condensate hose.
Position
Discription
2
Steam hose adapter
3
Connection control capsule
4
O-ring, steam hose adapter
5
Cover, cylinder
6
Control capsule / Water level
control
7
Clamping ring
8
Electrical Heater
9
Cylinder
10
Blow-down pump
11
Base
12
strainer insert
13
O-ring, base
14
Water inlet solenoid valve
15
O-ring, base
16
Pressure plate for heater ele-
ments
Содержание HeaterLine HL 12