Page 44
Warning:
Contacts laid between terminals 1 and 2 must be
potential free and rated for switching 24V AC or 208-240V AC
depending on the control voltage that is used (please see techni-
cal data on the unit's name plate).
Terminals Humidifier
7.5
Wiring Diagram
Please refer to the wiring diagram in the technical manual sup-
plied with the control used with your humidifier. Every steam
humidifier comes with a unit-specific technical manual and a
manual for the control. In addition, you will find downloadable
wiring diagrams and technical manuals at www.hygromatik.de.
7.6
Electrical Installation Checklist
Perform electrical installation checks in compliance with cus-
tomer site requirements and public power utility regulations:
Does the mains voltage match the voltage on the name
plate?
Have all electrical connections been made according to
the terminal diagram?
Have all electrical cable and plug connections been
properly tightened?
Are all electrical plug connections secure?
Is the unit grounded?
After this check the unit can be switched on.
Warning:
The unit must be closed and locked (only for humidifer
type HeaterLine). This guarantees that the cover is grounded.
Note:
For initial operation, control, service, malfunctions, and
circuit diagrams, consult the operation instructions for the Hygro-
Matik-controls or at www.hygromatik.de
.