Page 32
Connection condensate hose / hoses
Lay the condensate hose at an approximate incline of 5-10% to
the steam cylinder connection fitting, to allow the condensate to
drain freely.
Note:
It is recommended to form a loop of 200mm/7.9inch diame-
ter as a vapour trap provided there is enough space. Possible
operating noises can be reduced in this manner.
HL30 - HL45
HL6 -HL27
1.
2.
N1
P
O
3.
2.
3.
3.