No. Operation
Troubleshooting
Period
Result
15
Check whether the
display panel,
humidity and
temperature sensor
or cables is aging on
the surface.
Replace the components or
cables.
Semi-
annual
□Passed
□Failed
16
Use a high-precision
humidity and
temperature sensor
to calibrate the
humidity and
temperature sensors
inside and outside
the cabinet.
If the temperature deviation
is greater than 1°C or
humidity deviation is greater
than 5%, calibrate or replace
the humidity and
temperature sensor.
Semi-
annual
□Passed
□Failed
17
The heat exchanger
fins are not pushed
down.
Use a fin brush to organize
the fins that are pushed
down.
Semi-
annual
□Passed
□Failed
18
Check that the
thermal insulation
foam on the chilled
water pipe is intact.
Rewrap the thermal
insulation foam.
Semi-
annual
□Passed
□Failed
19
Check that the pipe
support is intact and
securely installed.
Secure the base.
Semi-
annual
□Passed
□Failed
20
Check that pipes do
not leak.
Close the water inlet stop
valve and repair leaks.
Semi-
annual
□Passed
□Failed
21
Check that the smart
cooling product
drainpipe is free from
leaks and blockages.
If the drainpipe leaks, repair
the leaks. If the drainpipe is
blocked, clear the blockage
inside the pipe.
Semi-
annual
□Passed
□Failed
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
6 System Operation and Maintenance
Issue 04 (2021-03-15)
Copyright © Huawei Technologies Co., Ltd.
131