Table 2-2 Pipe ports
Item
NetCol5000-C065
NetCol5000-C030/C032
Water outlet
pipe
G 1–1/2 inch internal thread
connector
G 1 inch internal thread
connector
Water inlet pipe
G 1–1/2 inch internal thread
connector
G 1 inch internal thread
connector
(Optional)
Humidifier water
inlet pipe
G 3/4 inch external thread
connector
G 3/4 inch external thread
connector
Drainpipe
BSPP 1/2 inch internal thread
connector
BSPP 1/2 inch internal
thread connector
Installation Requirements
Table 2-3 Installation requirements
Item
NetCol5000-C065
NetCol5000-C030/C032
Room
door
2 m high cabinet: width ≥ 1.2
m, height ≥ 2.3 m. The
cabinet may topple over in a
short time.
● 2 m high cabinet: width ≥ 1.2 m,
height ≥ 2.3 m. The cabinet may
topple over in a short time.
● 2.2 m high cabinet: width ≥ 1.2
m, height ≥ 2.5 m. The cabinet
may topple over in a short time.
Floor
Raised floor bearing capacity ≥ 530 kg/m
2
Raised floor height ≥ 250 mm
NOTE
If pipes are routed from the top, there is no requirement on the height of the
raised floor.
Pipe
routing
Bottom pipe routing or top and bottom pipe routing
Cabling
mode
Top cabling
Drainage
requirem
ents
Automatic drainage or forcible drainage
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
2 Product Description
Issue 04 (2021-03-15)
Copyright © Huawei Technologies Co., Ltd.