Table 3-3 Cables and switches required (NetCol5000-C065)
Name
Specifications
Quantity
Remarks
Power cable
Electronic|Electric Cable, 600 V/1000
V, ZA-RVV, 3 x 6 mm
2
, Black (3
Cores: Brown, Blue, Yellow/Green),
46 A, Outdoor Cable, CE
2 PCS
Optional;
same cable
parameters
for the
active and
standby
routes
Equipotential
ground cable
16 mm
2
outdoor copper cable
1 PCS
Engineerin
g
procureme
nt
Teamwork
networking
and
monitoring
cable
Signal Cable, Shielded Straight
Through Cable, 10 m, MP8-II,
CC4P0.5GY(S), MP8-II, FTP
1 PCS
Optional
Fuse
Slow Blow Fuse, 500 V, 3.15 A
2 PCS
Standard
configurati
on;
delivered
with the
product
OT terminal
Naked Crimping Terminal, OT, 6
mm
2
, M6, Tin Plating, Insulated Ring
Terminal, 12–10 AWG, Yellow
6 PCS
Standard
configurati
on;
delivered
with the
product
Cord end
terminal
Common Terminal, Single Cord End
Terminal, 6 mm
2
, 0.02 m, Insertion
Depth 12 mm, Black
12 PCS
Standard
configurati
on;
delivered
with the
product
Cable tie
G200IUV (3.6 x 200), Anti-
Ultraviolet And Anti-Freeze, Black
15 PCS
Standard
configurati
on;
delivered
with the
product
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
3 Installation
Issue 04 (2021-03-15)
Copyright © Huawei Technologies Co., Ltd.
39