v 1.6 - to be used from 28/09/2017 
 

 

Installation Manual (to run through set up), User manual (to change user settings - 

important

), Settings 

manual (to set up network controller), Laptop and RJ45 patch cable (to set up network controller). 

Important  Note:

  The  internal 

RCBO

  for  the  backup  outlet  is 

not  compliant

.  The  dedicated  backup 

socket outlet needs

 to have an 

RCD

Make yourself familiar with all 3 manuals before you go on site!  

Write down the 

serial numbers

 of the 

2 battery units, the battery enclosure and the network adapter

These will be required for activation and commissioning.  
(Refer to 

page 17 to 19

 of the 

Installation Manual

).  

Once  the  electrical  installation  is  done

  and  all  components  are  installed,  proceed  to  page  49  of  the 

installation manual 

 Setup. 

Page  50

  provides  a  very  useful  overview  of  the 

LED  indicators

  and  operation  buttons.  Use  the  LED 

indicators to check the status of the battery system.  

Pages 52 and 53

 of the installation manual show an 

overview of the menu (list of commands). 

Check that all wiring is correct!

 Turn ON the internal DC isolator and external AC supply and check that 

the power is supplied normally. Leave the Network Adaptor OFF. (See chapter 4,

 pages 55 ff 

installation 

manual).  

Set the date/time in order to activate the clock. (See chapter, 

pages 57  ff 

installation manual). 

This is 

crucial

  and  needs  to  be  done!  Please  double  check  time  and  date  have  been  set  correctly  (page  59 

installation manual). 

Set the operation parameters (See chapter 6 and 7, 

pages 60 ff

 installation manual) 

Network adapter communication 

- change network adaptor connection setting to 1 (1=connected) and 

leave communication ID at 1 (page 6 install. manual) 

Remaining Battery Level 

 always to be change to 

0%

.

 

Factory setting is either 0% or 40%. (

Page 65

)

 

Grid  Protection  Settings 

  PASSWORD  IS  "206"  - 

You'll  need  to  choose  the  correct  country  settings 

here. Enter password 206, under no 4.00 change value to ST 2! 

(pages 68 - 70) 

Some  lines  companies  have  requirements  that  are  different  form  the  standard  4777  settings.  Please 
contact solarcity while you are on site if the installation is in an area that has different grid protection 
requirements! (021 025 67893, 027 349 1950 

 [email protected]).  