Menu
Parameter
Description
Setting Rule
Humidifying
function
The humidifying
function can be set to
Enable, Disable, or
Enabled when active
power.
Enable indicates that the
electric humidifier will be
started when the ambient
humidity is lower than the
certain humidity range of
the humidity set point.
Disable indicates that the
electric humidifier will not
be started. Enabled when
active power indicates
that the electric humidifier
will be started when the
main power is active and
the ambient humidity is
lower than the certain
humidity range of the
humidity set point.
Dehumidifying
function
The dehumidifying
function can be set to
Enable, Disable, or
Enabled when active
power.
Enable indicates that the
dehumidification function
will be enabled when the
ambient humidity exceeds
the certain humidity range
of the humidity set point.
Disable indicates that the
dehumidification function
will not be enabled.
Enabled when active
power indicates that the
dehumidification function
will be enabled when the
main power is active and
the ambient humidity
exceeds the certain
humidity range of the
humidity set point.
Floor water
overflow alarm
action
Set this parameter to
Shutdown,
Inactivity, Only
indoor fan running,
or Humidifier
stopped based on
site requirements.
Retain the default value.
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
4 Power-On Commissioning
Issue 04 (2021-03-15)
Copyright © Huawei Technologies Co., Ltd.
88