Figure 6-4 Removing a fan (NetCol5000-C030/C032)
Step 3 Install the new fan in a reverse order of the removal.
Step 4 Connect cables to the new fan and close the front door.
Step 5 Choose Maint > Fan Maintenance on the home screen of the display module to
locate the SN of the faulty fan, and tap Power On.
Step 6 Tap Maint > Performance Maint on the home screen and clear the fan runtime.
----End
6.4.4 Replacing a Wet Film Humidifier
Prerequisites
On the home page, choose Maint > Performance Maint to query the runtime of
the wet film humidifier. If the value is 8760 h, the system automatically generates
a message. You are advised to change the wet film humidifier now.
Context
Tool: Phillips screwdriver
Procedure
Step 1 Choose Settings > System Settings > System Control, and set Humid to Disable.
Step 2 Open the rear door, remove the air filter, and switch off general circuit breakers.
Step 3 Use a Phillips screwdriver to remove the screws and sheet metal fasteners.
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
6 System Operation and Maintenance
Issue 04 (2021-03-15)
Copyright © Huawei Technologies Co., Ltd.
158