Figure 4-19 Wizard startup flowchart
NO TICE
● If a floor water overflow alarm is generated, the default action is Shutdown. If
there is no need to shut down the unit, contact Huawei technical support.
Evaluate the risk, choose Settings > System Settings > System Control, and
set Water overflow alarm action to Inactivity, Only indoor fan running, or
Humidifier stopped.
● If an in-cabinet water overflow alarm is generated, the default action is
Humidifier stopped. If there is no need to stop the humidifier, contact Huawei
technical support. Evaluate the risk, choose Settings > System Settings >
System Control, and set Water overflow alarm action to Shutdown,
Inactivity, or Only indoor fan running.
4.6.2 Startup
Step 1 Tap Start on the home screen of the controller.
●
If the screen shown in
is displayed, indicating initial startup,
perform
for initial startup verification.
Figure 4-20 Initial startup
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
4 Power-On Commissioning
Issue 04 (2021-03-15)
Copyright © Huawei Technologies Co., Ltd.
113