Alarm
ID
Alarm Name
Alar
m
Seve
rity
Possible Cause
Solution
A28F-0
4
Compressor
drive power
supply
abnormal
MAJ
OR
1. The cables to
phase U of the
compressor drive
are loose or
damaged.
2. The compressor
drive is faulty.
1. Check the cables to
the compressor drive.
2. Maintain or replace
the compressor drive.
A28F-0
8
Compressor
drive power
supply
abnormal
MAJ
OR
1. The cables to
phase V of the
compressor drive
are loose or
damaged.
2. The compressor
drive is faulty.
1. Check the cables to
the compressor drive.
2. Maintain or replace
the compressor drive.
A28F-1
0
Compressor
drive power
supply
abnormal
MAJ
OR
1. The cables to
phase W of the
compressor drive
are loose or
damaged.
2. The compressor
drive is faulty.
1. Check the cables to
the compressor drive.
2. Maintain or replace
the compressor drive.
A291-0
1
Compressor
overcurrent
alarm
MAJ
OR
1. The compressor
lacks oil.
2. The condenser
fins are dirty or
blocked.
3. The outdoor fan
is abnormal.
4. The refrigerant
is overfilled.
5. The compressor
is faulty.
1. Fill oil to the
compressor.
2. Clean the condenser
fins.
3. Maintain or replace
the outdoor fan.
4. Decrease certain
amount of refrigerant.
5. Maintain or replace
the compressor.