Menu Item
Parameter
Recorded Value
Number of running
systems in this group
8.1.2 Monthly Maintenance
lists the monthly maintenance items for the indoor unit. Record the
maintenance result in the table after checking each maintenance item.
Table 8-2 Monthly maintenance checklist
Item
Expected Result
Troubleshooting
Air
filter
The air filter is clean and not
blocked.
Replace the air filter. It is
recommended that an air filter
should be replaced every 6 months.
The air filter is not damaged or
distorted.
Replace the air filter. It is
recommended that an air filter
should be replaced every 6 months.
Conde
nsate
pan
and
liquid
level
detect
or
The condensate pan and liquid
level detector have no scale.
Clean up the scale from the
condensate pan and liquid level
detector.
Compr
essor
The compressor is secured.
Tighten screws if the compressor is
not secured.
The compressor service valve
has no oil stains.
Clean up the oil stains.
The operating compressor
generates no metal friction
noise or collision noise from
inside.
Replace the compressor.
Wet
film
humidif
ier
The wet film has no scale.
Replace the wet film humidifier.
No operating overtime alarm is
generated for the wet film
humidifier.
Replace the wet film humidifier.
Pipe
The refrigerant pipe does not
leak or corrode, and the
wrapped thermal insulation
foam is intact.
Repair the leakage points and
rewrap thermal insulation foam.