Menu
Parameter
Description
Setting Guide
Settings >
Quick Settings
> Teamwork
Settings
Teamwork
group No.
Specifies the teamwork
group number. The
teamwork group
numbers in the same
group must be the
same. A maximum of
four groups (1–4) can
be set.
Smart cooling
products in the
same aisle (or in
the same area) can
be grouped and use
the same group
number.
System
address
The addresses of units
in the same teamwork
group cannot be the
same.
Set the planned
unit address.
Teamwork
function
Specifies whether to
enable the teamwork
function. If no, the unit
operates
independently. If yes,
the unit operates in a
team with other units.
Set this parameter
based on the onsite
device heat
distribution.
Networking
mode
Specifies the
networking mode for
teamwork control. The
networking mode
selected on the screen
must match the actual
networking mode.
Otherwise, the
teamwork function is
unavailable. CAN
network indicates
teamwork control over
a CAN bus. MAC_CAN
network indicates
teamwork control over
an FE port.
CAN network
Settings >
Quick Settings
> System
Optional Parts
Cold aisle
sensor 1–5
If a temperature and
humidity sensor
outside the cabinet is
installed, set the
temperature and
humidity sensor in the
corresponding position
to Enable.
Disable
Hot aisle
sensor 1–5
Disable
Low
temperature
component
Specifies whether a
low temperature
component is used.
-
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
6 Power-On Commissioning
Issue 08 (2021-09-17)
Copyright © Huawei Technologies Co., Ltd.