Appearance
DP Port
Connects to the display module for communication and
power supply.
Button
Exterior
SW button
When the smart cooling product is shut down and the
admin user has logged in, if you hold down the button for
more than 10s, a red frame is added to the button that
involves a risky operation on the display module within 5
minutes. You can press and hold down the button for 10s
to enter the risky operation screen. Exercise caution
because a risky operation may affect system data.
2.2.4 Outdoor Unit
Appearance
Figure 2-8 NetCol500-A
Features
●
The outdoor unit is equipped with a high-efficiency variable-frequency drive
axial fan and the distinctive sickle blades adopt the owl-inspired fan blade
design to implement big air volume, low noise, and high efficiency.
●
The outdoor unit has excellent waterproof performance and meets IPX5
requirements.
●
The outdoor unit adopts the variable-frequency drive. The outdoor fan speed
is adjustable from 10% to 100%. The minimum operating frequency of the
fan is no greater than 5 Hz. The outdoor unit is running more steadily at low
loads.
●
Adopted the galvanized sheet and surface phosphati powder coating
techniques, the outdoor unit adapts to harsh environments with its sound
rigidity and anticorrosion performance.
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
2 Product Description
Issue 08 (2021-09-17)
Copyright © Huawei Technologies Co., Ltd.
24