Paramete
r
Description
Setting Rule
Default
Value
Number
of running
systems in
this group
Specifies the number of
running units in this group.
The value is an integer
ranging from 1 to the value
of Number of systems in
this group.
The master unit
assigns running units
in ascending order of
the addresses. The
address should be in
the range of 1–32. The
remaining units are
automatically
classified as standby
devices.
2
Rotation
function
Indicates whether to allow
the smart cooling products
to work as the standby
device in turn, maximizing
their service life.
It is recommended
that the function be
enabled when the
load is even.
Disable
Rotation
period
Rotation days (1–30).
7 by default
7 day (s)
Rotation
time
24 hours in a day (0–23).
0 by default
0
Forced
rotation
Indicates whether to enable
forced rotation regardless
of the specified rotation
time. After a forced
rotation, the rotation period
starts again.
This item is set to No
by default. If forced
rotation is required,
the function is set to
Yes.
No
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
6 Power-On Commissioning
Issue 08 (2021-09-17)
Copyright © Huawei Technologies Co., Ltd.