Procedure
Step 1 Check whether a low temperature component is installed on the outdoor side.
●
If no low temperature component is installed on the outdoor side, connect the
pressure gauge and vacuum pump at the low-pressure and exhaust pipe
needle valves to vacuumize the system simultaneously, as shown in
Figure 6-1 Vacuumizing the system without a low temperature component
(1) Vacuum pump
(2) Pressure gauge
(3) Low-pressure needle valve
(4) Exhaust pipe needle valve
●
If a low-temperature component is installed on the outdoor side, connect the
pressure gauge and vacuum pump at the low-pressure, exhaust pipe, and
liquid pipe needle valves to vacuumize the system simultaneously, as shown
in
.
Figure 6-2 Vacuumizing the system with a low temperature component
(1) Vacuum pump
(2) Pressure gauge 1
(3) Pressure gauge 2
(4) Low-pressure needle valve (5) Exhaust pipe needle valve (6) Liquid pipe needle valve
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual