Figure 11-35 Installing a liquid level detector
Step 7 Install the water pan cover, and close the front door.
Step 8 Power on the device and tap Startup on the home screen. Ensure that the smart
cooling product is running normally without any alarms.
----End
11.11 Replacing a Condensate Pump
Prerequisites
●
A condensate pump needs to be replaced.
●
A spare condensate pump of the same model is available and functional.
●
Tools: Phillips screwdriver, flat-head screwdriver, socket wrench
NO TICE
Before removing the condensate pump, drain water from the water pan
completely.
Context
The condensate pump can be maintained only from the front door.
Procedure
Step 1 Tap Shutdown on the home screen of the controller, and turn off the active power
switch QF1 and standby power switch QF2. (For the model with a single power
supply, you do not need to turn off QF2.)
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
11 Parts Replacement
Issue 08 (2021-09-17)
Copyright © Huawei Technologies Co., Ltd.
279