Item
NetCol5000-A050
Recommended cable
5 x 10 mm
2
Air cooling outdoor unit
power cable
Recommended cable
5 x 2.5 mm
2
(The neutral
wire is not used at the
customer's site.)
Water cooling outdoor
unit power cable
Recommended cable
3 x 1.5 mm
2
Water cooling module
power cable
Recommended cable
3 x 1.5 mm
2
Teamwork control
network cable
(mandatory for
teamwork networking)
Recommended cable
8-pin standard network
cable
Power cable for the low
temperature component
(mandatory when a low
temperature component
is configured)
Recommended cable
2 x 1.5 mm
2
Water cooling module
and outdoor unit
communications cable
(mandatory when the
outdoor unit is equipped
with an intelligent
temperature monitoring
board)
Recommended cable
3 x 1.5 mm
2
shielded
outdoor cable (Electrical
power cable, 300 V,
SJTW, 3 x 16 AWG, black
(three cores: black,
white, and green), 10 A,
shielded outdoor cable,
UL)
Equipotential ground
cable
Recommended cable
16 mm
2
outdoor copper
cable
NO TE
The cable flame spread rating must be at least VB.
When selecting, connecting, and routing cables, follow local safety regulations and rules.
When the external conditions such as cable routing or ambient temperature change,
perform verification in accordance with the IEC 60364-5-52 or local regulations.
The recommended cables are used only when the following requirements are met:
● Routing mode: The cables are routed over a tray or bracket in a single layer (E or F in
IEC 60364-5-523).
● The AC voltage loss is less than 3%.
● Single- or multi-core 90°C-resistant copper flexible cables are used.
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
4 Installation
Issue 08 (2021-09-17)
Copyright © Huawei Technologies Co., Ltd.
58