Alarm
ID
Alarm Name
Alar
m
Seve
rity
Possible Cause
Solution
A27C-0
1
Hot aisle 4
temp/humid
sensor fault
MAJ
OR
1. The cables to
the temperature
and humidity
sensor are loose or
damaged.
2. The
temperature and
humidity sensor is
faulty.
1. Check the cables to
the temperature and
humidity sensor.
2. Maintain or replace
the temperature and
humidity sensor.
A27C-0
2
Hot aisle 4
temp/humid
sensor fault
MAJ
OR
1. The cables to
the temperature
and humidity
sensor are loose or
damaged.
2. The
temperature and
humidity sensor is
faulty.
1. Check the cables to
the temperature and
humidity sensor.
2. Maintain or replace
the temperature and
humidity sensor.
A27C-0
1
Hot aisle 5
temp/humid
sensor fault
MAJ
OR
1. The cables to
the temperature
and humidity
sensor are loose or
damaged.
2. The
temperature and
humidity sensor is
faulty.
1. Check the cables to
the temperature and
humidity sensor.
2. Maintain or replace
the temperature and
humidity sensor.
A27C-0
2
Hot aisle 5
temp/humid
sensor fault
MAJ
OR
1. The cables to
the temperature
and humidity
sensor are loose or
damaged.
2. The
temperature and
humidity sensor is
faulty.
1. Check the cables to
the temperature and
humidity sensor.
2. Maintain or replace
the temperature and
humidity sensor.
A27F-0
2
Water
overflow
alarm
CRITI
CAL
The water
overflow sensor
detects water or
the sensor is
faulty.
1. While configuring the
water overflow sensor,
check and clear the
water source, and
maintain or replace the
sensor.
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
9 Alarm Reference
Issue 08 (2021-09-17)
Copyright © Huawei Technologies Co., Ltd.
219