Locati
on
Display Name Addr
ess
DIP Switch Sequence No.
1
2
3
4
5
6
Cold
aisle
Cold aisle 1
temp/humid
11
ON
ON
OFF
ON
OFF
OFF
Cold aisle 2
temp/humid
12
OFF
OFF
ON
ON
OFF
OFF
Cold aisle 3
temp/humid
13
ON
OFF
ON
ON
OFF
OFF
Cold aisle 4
temp/humid
14
OFF
ON
ON
ON
OFF
OFF
Cold aisle 5
temp/humid
15
ON
ON
ON
ON
OFF
OFF
Hot
aisle
Hot aisle 1
temp/humid
21
ON
OFF
ON
OFF
ON
OFF
Hot aisle 2
temp/humid
22
OFF
ON
ON
OFF
ON
OFF
Hot aisle 3
temp/humid
23
ON
ON
ON
OFF
ON
OFF
Hot aisle 4
temp/humid
24
OFF
OFF
OFF
ON
ON
OFF
Hot aisle 5
temp/humid
25
ON
OFF
OFF
ON
ON
OFF
NO TICE
After the addresses are set, power on the device, choose Settings > System
Settings > T/H Sensor on the home screen, and set the sensors in the aisles
corresponding to the addresses to Enable. Otherwise, the sensors will not work.
----End
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
4 Installation
Issue 08 (2021-09-17)
Copyright © Huawei Technologies Co., Ltd.
110