Parameter
Description
Setting Guide
Floor water
overflow
alarm action
Set this parameter to
Shutdown, Inactivity,
Only indoor fan
running, or
Humidifier stopped
based on site
requirements.
Retain the default
value.
In-cabinet
water
overflow
alarm action
Set this parameter to
Shutdown, Inactivity,
Only indoor fan
running, or
Humidifier stopped
based on site
requirements.
Retain the default
value.
Settings >
Quick Settings
> T/H Sensor
Temperature
and humidity
control type
Cold aisle, Hot aisle,
Return air, and Supply
air can be set as
required. Enable the
corresponding sensors
based on the control
type.
● When the
application
scenario is cold
or hot aisle
containment,
you are advised
to choose Cold
aisle if cold aisle
T/H sensors are
configured.
Choose Supply
air if no cold
aisle T/H sensors
are configured.
● When the
application
scenario is non-
aisle
containment,
you are advised
to choose
Return air.
Choose Cold
aisle if cold aisle
T/H sensors are
configured.
● You are not
advised to set
this parameter
as Hot aisle.
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
6 Power-On Commissioning
Issue 08 (2021-09-17)
Copyright © Huawei Technologies Co., Ltd.
135