Alarm
ID
Alarm Name
Alar
m
Seve
rity
Possible Cause
Solution
A282-0
8
Backup power
phase
sequence
abnormal
MAJ
OR
1. The power grid
is unstable.
2. The phase B
input cable is
faulty.
1. Check the power
grid.
2. Rectify the fault of
the phase B input cable.
A282-1
0
Backup power
phase
sequence
abnormal
MAJ
OR
1. The power grid
is unstable.
2. The phase C
input cable is
faulty.
1. Check the power
grid.
2. Rectify the fault of
the phase C input cable.
A28B-0
1
Compressor
high discharge
temperature
alarm
MAJ
OR
1. The refrigerant
leaks.
2. The condenser
fins are dirty or
blocked.
3. The ambient
temperature
exceeds the upper
threshold.
4. The
temperature
displayed by the
exhaust air
temperature
sensor is different
from the actual
temperature.
5. The input power
of the outdoor
unit has an open
phase, incorrect
phase sequence,
or is unavailable.
6. Cables to the
indoor or outdoor
fan are not
properly
connected.
7. The outdoor fan
or its drive is
faulty.
8. The exhaust fan
is faulty.
1. Identify and repair
the leaking point, and
refill refrigerant after
maintenance.
2. Clean the condenser
fins.
3. Measure the ambient
temperature.
4. Calibrate or replace
the temperature sensor.
5. Check the input
power of the outdoor
unit.
6. Check the cables to
the indoor and outdoor
fans.
7. Maintain or replace
the outdoor fan or its
drive.
8. Maintain or replace
the exhaust fan.