Alarm
ID
Alarm Name
Alar
m
Seve
rity
Possible Cause
Solution
A179-0
1
Humidifier
function
abnormal
alarm
MAJ
OR
1. The humidifier
pump inlet is
blocked.
2. The float does
not drop because
the humidifier
float is faulty.
3. The cable to the
humidifier pump is
not connected
properly.
4. The humidifier
pump is faulty.
5. The water pump
is blocked.
1. Clear the blockage
from the humidifier
pump inlet.
2. Maintain the
humidifier float.
3. Check the cable
connection to the
humidifier pump.
4. Replace the
humidifier pump.
5. Replace the water
pump.
A180-0
1
Humidifier
exceed
runtime alarm
WAR
NIN
G
The accumulated
runtime of the wet
film of the
humidifier exceeds
the alarm
threshold.
1. Maintain or replace
the wet film of the
humidifier and clear the
accumulated runtime.
A182-0
1
Humidifier
water supply
abnormal
alarm
MAJ
OR
1. The humidifier
water supply is
insufficient.
2. The float does
not float because
the humidifier
float is faulty.
3. The cable to the
humidifier float is
not connected
properly.
4. The cable to the
humidifier water
inlet solenoid
valve is not
connected
properly.
5. The humidifier
water inlet
solenoid valve is
faulty.
1. Check the humidifier
water supply.
2. Maintain the
humidifier float.
3. Check the cable
connection to the
humidifier float.
4. Check the cable
connection to the
humidifier water inlet
solenoid valve.
5. Replace the
humidifier water inlet
solenoid valve.
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
9 Alarm Reference
Issue 08 (2021-09-17)
Copyright © Huawei Technologies Co., Ltd.
210