During this whole phase, do not disconnect the
measuring terminals of the instrument from the system
At the end of the test, if the tripping current is within the
values of the table in the relevant § 11.1 the instrument
displays the
symbol to indicate the positive
outcome of the test and displays a screen like the one
to the side.
Press again the
GO/STOP
key
for a few seconds
to
repeat the test
Press the
SAVE
key or touch the icon
for the
partial saving of the test. The instrument shows the
message shown in the followed screen for a few
seconds
60
Restore the EVSE system as follows
:
Move CP State selector
A
Move CP State selector
C
If the RCD trip-out reset it
Press the icon
to continue with the next test (point
63)
61 At the end of the test, if the tripping current is not within
the values of the table in the relevant § 11.1, the
instrument displays the
symbol to indicate the
negative outcome of the test and displays a screen like
the one to the side.
Press again the
GO/STOP
key
for a few seconds
to
repeat the test
Press the
SAVE
key or touch the icon
for the
partial saving of the test and to
end the test
sequence
. The instrument shows the message shown
in the followed screen for a few seconds
62 Repeat the sequence again if necessary