During this whole phase, do not disconnect the
measuring terminals of the instrument from the system
.
At the end of the test, if the tripping current is within the
values of the table in the relevant § 11.1 the instrument
displays the
symbol to indicate the positive
outcome of the test and displays a screen like the one
to the side.
Press again the
GO/STOP
key
for a few seconds
to
repeat the test
Press the
SAVE
key or touch the icon
for the final
saving of the test on EVSE system (see § 7.1)
68 At the end of the test, if the tripping current is not within
the values of the table in the relevant § 11.1, the
instrument displays the
symbol to indicate the
negative outcome of the test and displays a screen like
the one to the side.
Press again the
GO/STOP
key
for a few seconds
to
repeat the test
Press the
SAVE
key or touch the icon
for the
partial saving of the test and to
end the test
sequence
. The instrument shows the message shown
in the followed screen for a few seconds
69 Repeat the sequence again if necessary