Gx
Series
EN - 120
Test 5
Test of RCD type A of EVSE system
55
Connect the instrument to the adapter as shown in the
diagram on the display (input
B4
on input
N,
input
B3
on input
E
and input
B1
on input
L1
)
.
Act on the three
adapter selectors by setting the followed positions
as shown by the instrument by flashing red/blue
indications
:
PP State
13A,20A,32A or 63A
CP State
C
Fault
OK
Press the icon
to continue with the test or press the
icon
to exit the test and return to the initial screen
56
The test is performed by the instrument considering
only General RCD of STD (G) type, type A and in
Ramp mode (
) 0°
.Touch the second icon. The
followed screen is shown on the display
57 Move the third slide bar reference by selecting the
desired rated current of the differential switch between
the options:
6,10, 30, 100, 300, 500, 650mA
Press the icon
to continue with the test or press the
icon
to exit the test and return to the previous
screen
.
Touch the third icon. The followed screen is
shown on the display
58
Ramp mode is fixed on the instrument
. Move the
reference of the lower sliding bar by selecting the type
of display of the tripping current during the ramp test
between the "
NOM
" or "
REAL
" options (see § 6.3)
Press the icon
to continue with the test or press the
icon
to exit the test and return to the previous
screen
.
Press the
GO/STOP key for a few seconds
. The
followed screen is shown on the display