Gx
Series
EN - 106
7. The value of the result is shown in the upper part of the
screen while the partial values of the tests with inverted
polarity of the test source in addition to the actual test
currents are shown in the fields "R +" and "R-"
The symbol
indicates the correct result of the
measurement.
Press again the
GO/STOP
key to repeat the test
Press
SAVE
key or touch the icon
for the partial
saving of the test and to continue with the next test
(point 10)
8. At the end of the test if the value of the measured
resistance is higher than the limit set, the screen
to the
side
is shown on the display. The value is shown in red
and the symbol
indicates the non-ok result of the
measurement. The indication ">1999
" indicates the
out of scale of the instrument.
Press again the
GO/STOP
key to repeat the test
Press the
SAVE
key or touch the icon
for the
partial saving of the test and to
end the test sequence
.
The instrument shows the message shown in the
followed screen for a few seconds
9. Repeat the sequence again if necessary