Gx
Series
EN - 49
Mode
- Verify of protection coordination
6.4.6.
1. Select the reference country (see § 5.1.2), the options
“TN, TT or “IT”, “25 or 50V”, “50Hz or 60Hz” and the
reference voltage in the general settings of the
instrument (see § 5.1.4).
NOTE: for “USA” country
the TT and IT systems are not available
Touch the
icon. The screen to the side appears
on the display.
Touch the lower icon. The following screen appears on
the display:
2. Move the left slide bar reference by selecting the
icon to execute the measurement only with the
instrument or the
icon to execute the
measurement with the inst optional accessory
IMP57 (see § 6.4.13).
Move the central slide bar reference by selecting the
“
L-L
”, “
L-N
” or “
L-PE
” options (for TN systems only).
Move the right slide bar reference by selecting the "
" option.
Touch the icon in the bottom center to set the
protection type and its rated current. The following
screen appears on the display:
3. Move the slide bar reference by selecting the type of
protection (Fuse of type
gG
or
aM
or magnetothermal
MCB in curve
B, C, K, D
), (Fuse of type
BS88-2
,
BS88-
3
,
BS3036
,
BS1362
or magnetothermal MCB in curve
B, C, D – UK
country). For
AUS/NZ
country
magnetothermal MCB in curve
B, C, D
Touch the “In” field. The following screen appears on
the display:
4. Touch the icon to zero the value in the In field and
use the virtual keyboard to set the value of the RCD
rated current within the values allowed by the
instrument.
Confirm the choice by going back to the previous
screen.
Touch the icon in the lower right corner to set the
tripping time of the RCD. The following screen appears
on the display: