Gx
Series
EN - 136
MEASUREMENT OF NETWORK PARAMETERS AND HARMONICS
Voltage
Range [V]
Resolution [V]
Accuracy
15.0
459.9
0.1V
(1.0
rdg + 1dgt)
Crest factor
1,5 ; Frequency: 42.5
69.0 Hz
Frequency
Range [Hz]
Resolution [Hz]
Accuracy
42.5
69.0
0.01
(2.0
rdg + 2dgt)
Allowed voltage: 15.0
459.9V ; Allowed current: 5%FS clamp
FS clamp
AC Current
FS clamp
Range [A]
Resolution [A]
Accuracy
10A
5% FS
9.99
0.01
1Ph:
(1.0
rdg + 3 dgt)
3Ph:
(2.0
rdg + 5 dgt)
10A
FS
200
5% FS
199.9
0.1
200A
FS
3000
5% FS
2999
1
Range:
5
999.9 mV, values under 5mV are zeroed
Crest factor
3; Frequency: 42.5
69.0 Hz
Active power (@ 230V in 1Ph systems, 400V in 3Ph systems, cos
=1, f=50.0Hz)
FS clamp
Range [kW]
Resolution [kW]
Accuracy
10A
0.000
9.999
0.001
1Ph:
(2.0
rdg + 5 rdg)
3Ph:
(2.5
rdg + 8 rdg)
10A
FS
200
0.00
999.99
0.01
200A
FS
1000
0.0
999.9
0.1
1000A
FS
3000
0
9999
1
Reactive power (@ 230V in 1Ph systems, 400V in 3Ph systems, cos
=0, f=50.0Hz)
FS clamp
Range [kVAr]
Resolution [kVAr]
Accuracy
10A
0.000
9.999
0.001
1Ph:
(2.0
rdg + 7 rdg)
3Ph:
(3.0
rdg + 8 rdg)
10A
FS
200
0.00
999.99
0.01
200A
FS
1000
0.0
999.9
0.1
1000A
FS
3000
0
9999
1
Power factor (@ 230V in 1Ph systems, 400V in 3Ph systems, f=50.0Hz)
Range Resolution
Accuracy
0.70c
1.00
0.70i
0.01
(4.0
rdg + 10rdg) if I
10%FS
(2.0
rdg + 3rdg) if I > 10%FS
cos
(@ 230V in 1Ph systems, 400V in 3Ph systems, f=50.0Hz)
Range Resolution
Accuracy
0.70c
1.00
0.70i
0.01
(4.0
rdg + 10rdg) if I
10%FS
(1.0
rdg + 7rdg) if I > 10%FS
Voltage harmonics (@ 230V in 1Ph systems, 400V in 3Ph systems, f=50.0Hz)
Range [%]
Resolution [%]
Ordine
Accuracy
0.1
100.0
0.1
01
25
(5.0
rdg + 5rdg)
Fundamental frequency: 42.5
69.0 Hz, DC accuracy not declared
Current harmonics (f=50Hz)
Range [%]
Resolution [%]
Order
Accuracy
0.1
100.0
0.1
01
9
(5.0
rdg + 5rdg)
10
17
(10.0
rdg + 5rdg)
18
25
(15.0
rdg + 10rdg)