Gx
Series
EN - 114
32
If the test fails, the screen like the one on the side is
shown on the display. The incorrect value of the
parameter is shown in red and the symbol
indicates
the non-ok result of the measurement
.
Press again the
GO/STOP
key to repeat the test
Press the
SAVE
key or touch the icon
for the
partial saving of the test and to
end the test sequence
.
The instrument shows the message shown in the
followed screen for a few seconds
33 Repeat the sequence again if necessary
34
In case of EVSE system in ventilated environment
,
act on the three selector switches of the adapter by
setting the followed positions as shown by the
instrument with flashing red / blue indications
:
PP State
13A,20A,32A or 63A
CP State
D
Fault
OK
NOTE: the EVSE station should have the possibility
to activate manually or automatically the forced
ventilation system
Press the icon
to activate the
test on D state
. The
following screen is shown on the display
Press the icon
to exit the test and return to the
initial screen
35
The result of the measurement is shown in the screen
to the side
. The symbol
indicates the correct result
of the measurement.
The symbol
also indicates a
positive result of the measurement but with values
outside the limits present in the Table 4
Press again the
GO/STOP
key to repeat the test
Press the
SAVE
key or touch the icon
for the
partial saving of the test and follows with the next test
of PE fault simulation
(point 38)
Press again the
GO/STOP
key to repeat the test