GSC53N - GSC57 - ZG47
EN - 60
The
message
"
Rp
high
" indicates that the
instrument
can't
measure correctly the
Voltage from Auxiliary
Earth rod. Check that
the
terminals
are
correctly connected and
the Auxiliary earth rod
connected to B2 (red
conductor) has not been
inserted in a pebbly or
poor conductive ground.
If necessary pour some
water around the rod.
EARTH
05.06.01
- - -
Vd= 1V
Test:04
RAVG=0.74
Rp HIGH
3-W
Message
"Rp":
Check
Auxiliary Earth rods.
FUNC CLR
The message "
Rp and
Rc high
" indicates that
the instrument can't
measure correctly the
Voltage from Auxiliary
Earth rod and can't flow
the minimum current for
measurement.
Check
that the terminals are
correctly connected.
Check if the Auxiliary
earth rod connected to
B2 (red conductor) and
B4(blue conductor) has
not been inserted in a
pebbly
or
poor
conductive ground. If
necessary pour some
water around the rod.
EARTH
05.06.01
- - -
Vd= 1V
Test:04
RAVG=0.74
Rp and Rc HIGH
3-W
Message "Rp and Rc HIGH":
Check Auxiliary Earth rods.
FUNC CLR
THE PREVIOUS RESULTS CANNOT BE SAVED
.