6.6.1. Measurement Procedure and Result of "RMEAS" mode
1. Select the "
RMEAS
" mode by means of the
F1
key.
2. Connect the test leads to
B1, B2, B3, B4
input terminals according to the
following picture:
B2
B3
B4
B1
I1
I2
I3
230V~
50Hz
1.3A
Connection of the test leads during LOW 10A test.
3. Set the resistance limit value by mean the
F3
and
F4
keys.
4. Connect the 230V~ 50Hz Power supply socket of the instrument to a power socket
using the C5700 cable.
5. Press the
START
key. The instrument will execute the measurement..
WARNING
If the instrument displays
"Measuring"
it means that it is effecting the
measurement. During this phase the instrument test leads are not to be
disconnected.
At the end of the test the
instrument
emits
an
acoustic
signal
and
display
the
screen
alongside.
LOW 10A
05.06.01
Resistance value
0.107
13.4A
RMEAS RLIM:0.150
Test Current Value
FUNC
Working mode
The displayed result can be stored pressing the
SAVE
key
twice
(according to
paragraph 9.1).
START
STOP