GSC53N - GSC57 - ZG47
EN - 33
6.3.2.4. Results of "RAMP
" mode
4. Press the
START
key
once
to execute a test with 0° Current waveform.
or
Press the
START
key
twice
to execute a test with 180° Current waveform.
The instrument generates a leakage current growing step by step for a given
time interval.
WARNING
Never disconnect the test leads from the circuit under test when the
message
" MEASURING "
is displayed.
At the end of the test if
the RCD tripping current
is lower than I
n
(Type
AC) or 1.4I
n
(Type A
with I
n
>10mA) or 2I
n
(Type A with I
n
10mA),
the instrument emits a
double sound signal
indicating the positive
outcome of the test and
displays
the
screen
alongside.
Tripping Current
RCD
05.06.01
Tripping time (expressed in
milliseconds).
27
mA
35ms
FRQ=50.0Hz Ut= 1V
VP-N=231V VP-PE=231V
RCD OK
30mA
50V
Value of contact voltage
U
t
detected referred to the
rated value of the RCD
current set.
OK:
RCD passed the test.
FUNC IdN
RCD
UL
Contact Voltage Limit value
Working mode
RCD nominal current
RCD type
5. The test can be stored pressing the
SAVE
key
twice
(according to paragraph
START
STOP