GSC53N - GSC57 - ZG47
EN - 36
This screen is displayed
when
the
phase
conductor has been
exchanged
with
the
Protection Conductors.
The instrument does not
effect the test. Reverse
the phase to earth
connection in the plug or
exchange
the
black
cable with the green one
RCD
05.06.01
- - -
ms
FRQ=50.0Hz Ut= ---V
VP-N= 2V VP-PE= 230V
CHANGE P-PE
x1 30mA
50V
Phase and Protection
Conductors
are
exchanged.
FUNC IdN
RCD
UL
This screen is displayed
when in a 230V Phase
to Phase System the
blue
conductor
was
reversed with respect to
the green one.
The instrument does not
effect the test. Reverse
the blue and green
conductors.
RCD
05.06.01
- - -
ms
FRQ=50.0Hz Ut= ---V
VP-N=130V VP-PE= 227V
CHANGE N-PE
x1 30mA
50V
Neutral and Protection
Conductors
are
exchanged.
FUNC IdN
RCD
UL
If a contact voltage
U
t
higher
than
the
selected limit (U
L
)
is
detected, the instrument
interrupts the test and
emits
a long sound
signal
at the end of the
test and displays the
screen alongside.
RCD
05.06.01
- - -
ms
FRQ=50.0Hz Ut= ---V
VP-N=234V VP-PE= 234V
UT DANGEROUS
x1 30mA
50V
The instrument doesn't
detect
an
efficient
protection circuit.
FUNC IdN
RCD
UL
If the instrument detects
that the earth cable
(green)
is
not
connected, the screen
alongside is displayed
for 5 seconds then the
initial display is back.
Check the connections
of PE conductor under
test.
RCD
05.06.01
- - -
ms
FRQ =50.0Hz Ut= ---V
VP-N=234V VP-PE= 34V
NO PE
x1 30mA
50V
Message
“NO PE”
: the
instrument doesn't detect
an
efficient
protection
circuit.
FUNC IdN
RCD
UL