This screen is displayed
when
the
phase
conductor has been
exchanged
with
the
neutral one.
The instrument does not
effect the test. Reverse
the shuko plug or
exchange
the
black
cable with the blue one.
LOOP
05.06.01
- - -
---A
FRQ=50.0HZ
VP-N=231V VP-PE= 0V
CHANGE P-N
P-PE 50V
Phase
and
Neutral
Conductors
are
exchanged.
FUNC Z2
UL
This screen is displayed
when
the
phase
conductor has been
exchanged
with
the
Protection Conductors.
The instrument does not
effect the test. Reverse
the phase to earth
connection in the plug or
exchange
the
black
cable with the green one
LOOP
05.06.01
- - -
---A
FRQ=50.0HZ
VP-N= 1V VP-PE= 230V
CHANGE P-PE
P-N
Phase and Protection
Conductors
are
exchanged.
FUNC Z2
This screen is displayed
when in a 230V Phase
to Phase System the
blue
conductor
was
reversed with respect to
the green one.
The instrument does not
effect the test. Reverse
the blue and green
conductors.
LOOP
05.06.01
- - -
---A
FRQ=50.0HZ
VP-N=131V VP-PE= 227V
CHANGE N-PE
P-N
Neutral and Protection
Conductors
are
exchanged.
FUNC Z2